Page 84 
Example 4 Differential Control 
empty distance (P105), 3.5m  
85% , Pt 1, high alarm on (P213), 2.38m 
80% , Pt 1, high alarm off (P214), 2.24m 
15% , Pt 2, low alarm off (P254), 0.42m 
10% , Pt 2, low alarm on (P253), 0.28m 
5%, Diff control, on, (223) 0.14m 
1%, Diff. control, off, (P224) 0.03m 
Note 
When using the Advanced 5 to measure differential, the transducers should 
be installed at the same height, to ensure that no differential is present when 
the level is zero on both sides. If this is not possible then a measurement 
offset (P851) or Display Offset (P802) must be applied to ensure the correct 
reading is obtained. 
 
 
 
In this example the Advanced 5 is being used to control a rake on a screen, 
which is filtering out solids in the inlet flow to a wastewater treatment plant.  
A high alarm has been assigned to Pt 1 (Transducer 1), on the upstream 
side and a low alarm, to Pt 2 (Transducer 2) on the downstream side. The 
Diff. Control, to operate the rake is on relay 1, high alarm, on Transducer 1 
(upstream), is on relay 2 and, low alarm, on Transducer 2 (downstream) is 
on relay 3.