Page 200
Average Flow
P863 Average Flow
This parameter will display the Average Flow for the time period set in
Average Time (P864). It is read only and cannot be changed.
P864 Average Time
This parameter will set the time period over which the Average Flow (P863)
is to be calculated before being displayed.
Display Parameters
Options
P800 Display Units
This parameter determines whether the reading displayed is in
Measurement Units (P104), or as a percentage of span.
Option
Description
1 = Measured (Default)
Display is in selected units dependant in
Mode (P100)
2 = Percentage
Display is in percentage of span
dependant in Mode (P100).
P801 Decimal Places
This parameter determines the number of decimal places on the reading
during run mode.
Minimum = 0 (No decimal places), Maximum 3 = (3 decimal Places)
Default = 2 (2 decimal Places)
P802 Display Offset
The value of this parameter is added to the reading before it is displayed, in
Measurement Units (P104).
It does not affect the relay setpoints or the mA output, only the reading on
the display.
You could use this feature if for example you wanted to reference the
reading to sea level, where you would enter the distance between Empty
Level (P105) and sea level. If the empty level point is below sea level, then
enter a negative value.

Table of Contents

Other manuals for Pulsar ULTRA 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pulsar ULTRA 5 and is the answer not in the manual?

Pulsar ULTRA 5 Specifications

General IconGeneral
BrandPulsar
ModelULTRA 5
CategoryController
LanguageEnglish

Related product manuals