Pump “Advanced” Parameters 
When Ultra Wizard = 2 Pump/Differential 
The following parameters are used to set the “Advanced” Pump features.  
Pump Run On 
This feature is used to periodically allow the pumps to continue operating 
below  their  normal  “OFF”  point,  in  order  to  discharge  any  sediment  that 
may have settled at the bottom of the vessel. 
P349 Prime Level 
Sets the required level to ensure pumps are fully primed after a pump run on 
has  occurred.  Following  a  pump  run  on,  any  pump,  whose  “ON”  point  is 
below the Prime Level will be held  “OFF”  until the Prime Level has been 
exceeded. 
P350 Run Interval 
Set required time period, in hours, at which pump run on should occur. 
P351 Run Duration 
This parameter sets the length of time, in seconds, that pumps will run on 
for, it should be noted that only one run on is allowed per Run Interval. 
Starting 
This  feature  is  used  to  reduce  the  effects  of  power  surges,  caused  by 
switching of pumps, in the following instances, (P352) Power surge (mains 
or  hydraulic)  that  is  generated  when  multiple  pumps  are  started 
simultaneously, (P353) Power resumption following a power failure.  
P352 Start Delay 
Set the required time period, in seconds, that should elapse between pumps 
starting. Default = 10 seconds. 
P353 Power Delay 
Set the required time period, in seconds, that should elapse before pumps are 
allowed to start following a power failure. Default = 10 seconds.