Page 36 
Test Mode 
Test mode is used to simulate the application and confirm that all parameters 
and relay setpoints have been entered as expected. During simulation, there 
is a choice of whether the relays will change state (hard simulation) or not 
(soft simulation), but the LED’s will always change colour as programmed, 
and  the  mA  output  will  change  in  accordance  to  the  chosen  mode  of 
operation.  If  you  wish to  test  the  logic  of the  system  that  the  relays  are 
connected to then select hard simulation, but if you don’t wish to change 
the relay state, then select a soft simulation. 
There  are  two  simulation  modes,  automatic  and  manual.  Automatic 
simulation will move the level up and down between empty level or the pre-
determined  Start  Level  (P983)  and  Pump/Control  relay  switch  points,  if 
you wish to change the direction of the level movement e.g. to go beyond 
relay  setpoints,  this  can  be  done  by  using  the  arrow  keys.  In  manual 
simulation, using the arrow keys will allow you to move the level up and 
down as required. 
To  enter  simulation,  first  go  to  program mode.  Using  the  menu  system, 
select menu item ‘Test’, then sub-menu item ‘Simulation’. Simply change 
the value of the parameter P980 to one of the following: 
1= Manual soft simulation   
2= Automatic soft simulation   
3= Manual hard simulation   
4= Automatic hard simulation 
To return to program mode, press CANCEL and test mode will end. 
When in manual simulation, by default test mode will move the level by 
0.1m steps. Altering the increment (P981) will change this value. 
In automatic mode, the rate at which the level moves up and down is set by 
the increment (P981) in metres, the rate (P982) in minutes, which can be 
changed  to  make  the  level  move  up  and  down  faster.  E.g.  if  increment 
(P981) is set for 0.1m and rate (P982) is set to 1 min then the level will 
increase  or  decrease  at  a  rate  of  0.1m/min.  To  make  the  simulated  level 
move slower, decrease the value in increment (P981) or increase the value 
in rate (P982). To make the simulated level move faster, increase the value 
in increment (P981) or decrease the value in rate (P982).