P696 Reset Breakpoints 
This parameter allows the resetting, to the default value, of all previously set 
breakpoints (P610-673), without having to access them individually. When 
it is necessary to reset or amend particular breakpoints this can be achieved 
by  directly  accessing  the  desired  parameter  (P610-673)  and  changing  as 
required. 
P697Number of Breakpoints Set 
This parameter allows you to review the number of breakpoints that have 
been set,  without the need to access each individual one in turn, this is a 
“Read Only” parameter and no values can be entered.  
Pump Efficiency 
When Ultra Wizard = 2 Pump/Differential 
Set Up 
P187 Pump Eff.? 
This parameter determines whether pump efficiency is enabled or disabled. 
 
P188 Calib. Delay 
This parameter is used to set a delay, after all pumps have stopped, to allow 
for any turbulence of the material surface to settle prior to monitoring the 
level in the vessel and determining the inflow before the next pump cycle 
commences. The delay time is entered in seconds. Default = 45 seconds. 
Important Information 
When setting the time period for the Calibration Delay (P188) it is 
important that it does not exceed the time from when all pumps switch Off 
to the first pump Start during normal operation as it will prevent 
determining the Inflow and any subsequent calculation of Efficiency.