Page 229                                                                                                             
P982 Rate 
In automatic mode, the rate at which the level will move up and down is 
determined by distance, P981 Increment and the time, P982 Rate which by 
default is set to 1min and can be changed as required. To increase the rate 
at  which the  level  moves  increase  the  Increment  (P981)  or  decrease  the 
Rate (P982). To  decrease the rate at  which the level  moves decrease  the 
Increment (P981) or increase the Rate (P982). 
P983 Start Level 
When  using  automatic  simulation,  this  parameter  can  be  used  to  pre-
determine the point at which the simulated level will start at and return to. 
This  can  be  used  to  simulate  the  lowest  point  to  which  the  level  would 
normally operate. 
P984 Inc. Change 
When  using  automatic  simulation,  you  can  incrementally  increase  or 
decrease the rate whilst running simulation. The rate is increased /decreased 
incrementally  by  the  value  P984  (Incremental  Change)  by  using  the 
“decimal point” key to increase and the “plus/minus” key to decrease the 
rate of change.    Default = 0.1m 
Hardware 
P990 Self-Test 
If you enter 1 for this parameter, then the unit will perform a self-test. This 
will  confirm  that  the  various  parts  of the  circuitry are  working correctly. 
You  will see confirmation  messages that  the clock  and the EEPROM are 
working correctly, and error messages for any parts that fail. 
P991 Hard Test 
When this parameter is selected, the unit will test the following in turn. 
•  LED’s. Watch them change colour as shown on the display, and 
press, ENTER, if they operated as shown. 
•  Relays.  Press a numeric key corresponding to the number of the 
relay you wish to test, and the relay will change state each time the 
key is pressed. If you press any other key, other than a valid relay 
number, then the test will end. 
•  Segments. All the segments on the LCD are lit up, so you can see if 
they  all  work.  Press,  ENTER,  to  end  the  test.  The  LED’s  all  go 
green at the same time.