Page 180 
Pump Logs 
 
When Ultra Wizard = 2 Pump/Differential   
P510 Pump 1 Hours 
This  parameter  displays  the  current  total  running hours  for  Pump 1.  Any 
value from 0 - 9999 can be entered to facilitate any update to the stored total 
for any reason e.g. a replacement pump being fitted. 
P511 Pump 1 Starts 
This parameter displays the current total pump starts for Pump 1. Any value 
from 0 - 9999 can be entered to facilitate any update to the stored total for 
any reason e.g. a replacement pump being fitted. 
P512 Pump 1 Starts/Hour 
This  parameter  displays  the  current  pump  Starts/Hour  for  Pump  1.  Any 
value from 0 - 9999 can be entered to facilitate any update to the stored total 
for any reason e.g. a replacement pump being fitted. 
P513 Pump 1 Run On 
This parameter displays the current number of Pump Run On’s, which have 
occurred, for Pump 1. Any value from 0 - 9999 can be entered to facilitate 
any update to the stored total for any reason e.g. a replacement pump being 
fitted. 
P514 Pump 1 Draw 
This parameter displays the current Draw Rate for Pump 1, which is used to 
calculate the pump efficiency. Any value from 0 - 9999 can be entered to 
facilitate any update  to  the  stored  total for  any  reason  e.g.  a  replacement 
pump being fitted. 
P515 Pump 1 Efficiency 
This parameter displays the current value for Pump 1 Efficiency, which is 
used to calculate the pump efficiency and will update with any change to the 
Pump Draw Rate (P514).  
P516 - P521 Pump 2 
 These parameters contain the same information as above for Pump 2.