No dehumidication, air mover runs but compressor does not.
1. Bad connection in compressor circuit
2. Safety oat switch closed, check pump reservoir
3. Defective compressor capacitor
4. Defective compressor overload
5. Defective compressor
6. Defective control board
Air mover does not run. Compressor runs briey but cycles on and off.
1. Loose connection in blower circuit
2. Obstruction prevents impeller rotation
3. Defective air mover
Unit removes some water but not as much as expected.
1. Air temperature and/or humidity have dropped
2. Humidity meter and/or thermometer used are out of calibration
3. Unit has entered defrost cycle
4. Air lter dirty
5. Defective defrost thermistor
6. Low refrigerant charge
7. Defective compressor
8. Restrictive exhaust ducting
Unit runs but does not pump water.
1. Hose kinked or plugged
2. Pump motor defective
3. Pump check valve plugged
4. Bad connection in pump circuit
5. Hose disconnected internally
Unit pumps water automatically but not when PURGE button is pushed.
1. Bad connection in PURGE button circuit
2. Defective control board
Evaporator coil frosted continuously, low dehumidifying capacity.
1. Defrost thermistor loose or defective
2. Low refrigerant charge
3. Dirty air lter or restricted air ow
4. Front housing is not sealed to lower housing