Non-Cycling
Parts/Instruction Manual
This manual contains important safety information and should be made available to
all personnel who operate and/or maintain this product. Carefully read this manual
before attempting to operate or perform maintenance on this equipment.
Manual No. 65504-2A
January 2007 Edition
Update: May 2009

Questions and Answers

  • J
    julie60Aug 5, 2025
    What to do if my Quincy QPNC 125 Dehumidifier motor cuts out on overload?
    • W
      William MendozaAug 5, 2025
      If the motor cuts out on overload, it could be due to several reasons. First, the dryer might be operating outside of its specified range; in this case, verify the treated air's flow rate. Secondly, the dryer might be working under unfavorable conditions for an air-cooled condenser; make sure to clean the condenser. Finally, the cooling circuit could be malfunctioning due to an incorrect refrigerant charge; check for any refrigerant gas leaks.
  • S
    Sara ScottAug 9, 2025
    Why is my Quincy QPNC 125 Dehumidifier compressor head so hot?
    • B
      Bradley WalshAug 9, 2025
      If the compressor head is very hot, exceeding 131 °F (55 °C), it could be due to a few reasons. The dryer might be operating outside its rated capacity, so check the flow rate of the treated air. Additionally, the dryer may be working under poor conditions for the air-cooled condenser, so you should clean the condenser. It's also possible that the cooling circuit isn't working correctly due to an incorrect refrigerant charge, in which case you should check for leaks of refrigerating gas.
  • T
    Theresa TravisAug 13, 2025
    What to do if my Quincy QPNC 125 Dehumidifier compressor is very noisy?
    • M
      Maureen HoffmanAug 13, 2025
      If the compressor is very noisy, it indicates trouble with the internal mechanical parts or with the valves. You should consider repairing or replacing the affected components.
  • J
    Jose KennedyAug 17, 2025
    What to do if my Quincy QPNC 125 Dehumidifier motor hums and does not start?
    • Y
      ymitchellAug 18, 2025
      If the motor hums but doesn't start, it could be due to several reasons. First, the line voltage might be too low, in which case you should contact the electric power company. Second, the machine may have been switched off and on again too quickly, without allowing enough time for pressure balancing; wait a few minutes before restarting it. Lastly, the motor's starting system could be defective; check the running and starting relays and condensers, if installed.
  • B
    Brandy ChambersAug 22, 2025
    What to do if my Quincy QPNC 125 Dehumidifier machine stopped and does not restart?
    • R
      Ryan MackAug 22, 2025
      If the machine (compressor) has stopped and won't restart, it could be due to overload protection or a burned-out compressor motor. In the first case, refer to sections B2, B3, and C3 for remedies. In the second case, replace the compressor.
  • J
    jfreyAug 27, 2025
    Why is there condensate in the pipings of my Quincy QPNC 125?
    • A
      Andrea HicksAug 27, 2025
      The presence of condensate in the pipings may be due to several factors. The condensate separator might not be working correctly; in this case, clean the condensate drain filter. The dryer could be operating outside its specified range; check the flow rate of treated air. Also, the dryer might be working under bad conditions for the air-cooled condenser; make sure to clean the condenser.
  • L
    Leslie Stewart MDAug 30, 2025
    How to fix a Quincy QPNC 125 with no compressed air passing through the outlet?
    • N
      Natasha WileyAug 30, 2025
      If no compressed air passes through the dryer outlet, the pipes may be frozen inside. This could be because the hot gas bypass valve is broken or out of calibration, or because the room temperature is too low, causing the evaporator's piping to be obstructed with ice.

Summary

GENERAL INFORMATION

SAFETY MESSAGES

Cautions regarding dryer usage and potential hazards.

SAFETY ZONES, DEVICES AND DECALS

WARNINGS AND SAFETY DEVICE IDENTIFICATION

Identification and explanation of safety warnings, zones, and devices.

SAFETY INSTRUCTIONS

INSTALLATION INSTRUCTIONS

POSITIONING AND ELECTRICAL HOOKUP

Instructions for physical placement and electrical connection.

CONNECTION TO THE COMPRESSED AIR SYSTEM

START-UP AND OPERATION

MAINTENANCE

TROUBLESHOOTING