EasyManuals Logo

RAB Lighting FXLED78 User Manual

Default Icon
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
FXLED78 INSTALLATION INSTRUCTIONS
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
RAB xtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper
grounding is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE
INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT
AND THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF before installing or maintaining xture. No user serviceable
parts inside.
Thank you for buying RAB lighting xtures. Our goal is to design the best quality products to get the job done right. We’d like to hear your comments.
Call the Marketing Department at 888-RAB-1000, or email: marketing@rabweb.com
SLIPFITTER MOUNTING
1. The sliptter mounting ts a 2
3
/8” O.D. Tenon.
Place the sliptter over the Tenon and secure the
xture with the 2 Set Screws on the side of the
sliptter.
2. Remove 2 screws on side of Round Cover Plate.
Remove the Round Cover Plate and adjust the
angle of the xture.
3. Loosen the Locking Bolt and swivel xture to
desired angle.
4. Tighten the Locking Bolt and re-attach Round
Cover Plate.
Tenon
Set
Screws
Round
Cover
Plate
Locking
Bolt
Pivot Bolts
TRUNNION MOUNTING
CAUTION: UL and C-UL listed or CSA certied liquid
tight cord grip suitable for use with three conductor
type STW exible cord shall be used for connection
to a wet location outlet box provided by others.
To adjust the angle of the xture using the trunnion:
1. Loosen the Pivot Bolts & angle locking screw.
2. Adjust xture to desired angle.
3. Tighten Pivot Bolts & angle locking screw.
TROUBLESHOOTING
1. Check that the line voltage at the xture is correct.
Refer to wiring directions.
2. Is the xture grounded properly?
3. Is the photocell, if used, functioning properly?
WIRING
Universal voltage drivers permits operation at 120V to
277VAC, 50 or 60 Hz.
1. Connect the BLACK xture lead to the
(+) LINE supply lead.
2. Connect the WHITE xture lead to the
(-) COMMON supply lead.
3. Connect the bare copper Ground wire from xture
to supply ground.