Advanced Programming
6-2
Verbatim Owner's Manual
6.1.1 Notes for Programming Code Table:
Refer to these numbered items under the "Notes" column in the following
Programming Code Table.
1. ZZ = 2 digit channel number. Use ZZ=00 for Station ID message.
2. For any channels you have programmed as “Status Only” or “Run Time
Meter”, use code 1 ZZ for the Open Circuit message, use code 2 ZZ for
the Closed Circuit Message. See Section 6.2, “Programming Operations,”
for message information for any Pulse Totalizer channels.
3. DN (Designation Number) is 01 for first dialout phone number, 02 for
second number, etc. DN = 00 for special “callback” phone number. Use
MINUS to insert any needed delays between digits. Each such delay is 1
second unless extended using code 928.
4. Actual power failure trip delay may be a fraction of a second longer than
programmed value, due to power supply discharge time which varies with
the number of option boards.
I Caution:
5. If Alarm Reset Function is turned OFF, acknowledged alarms will
NEVER RE-ARM, preventing further alarm calls after acknowledgment
for each channel.
6. Speaker always operates during front panel programming, even if
programmed to be off.
7. Cannot be read or changed over the phone.
8. Does not change channels that have been configured for “Status Only,”
“Run Time Meter,” or “Pulse Totalizer.”
I Caution:
9. High Speed Dialing setting may not work reliably with some telephone
company exchanges.
10. Add POINT to restore default message.
11. To pre-set a Run Time value, include the value before ENTER.
12. Maximum value that can be entered is 4,294,967,294.
13. Omits all mention of disabled channel. Restore by setting for Normally
Closed, Normally Open, etc.