Page 240 Appendix A: Flow Meters
Observe which station takes the longest time for its GPM rate to
"settle." Round this time period to the next minute and use this
rounded value as the flow rate limit check delay.
Warning:
This delay value establishes the amount of time in
which a main or station line break can be detected
and subsequently shutdown.