EasyManua.ls Logo

R&D Wireless Rain Sensor - Wiring Scenarios; Power Wiring

R&D Wireless Rain Sensor
8 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A. Controllers with NO Sensor Inputs, NO Pump Start or
Master Valve: (Fig. 3)
Disconnect the common con-
trol wire from the common
terminal of the controller.
Join this wire to the White
Receiver control wire using a
wire nut. Attach the Brown
control wire (N/C) to the
common terminal on the con-
troller.
B. Controllers WITH Sensor Inputs: (Fig. 4)
Find the controller terminals marked “Sensor” or “SEN” and
directly connect the White & Brown wires to these two termi-
nals, in any order. There may be a jumper tab or wire that must
be removed from between the
terminals, or a “sensor con-
nected” switch that must be
activated. Note: If the con-
troller requires a Normally
Open sensor circuit (such as
the Toro Greenkeeper
TM
or
Toro ECx
TM
), attach the White
and Green wires to the termi-
nals.
C. Controllers WITH Pump Start or Master Valve: (Fig. 5)
Similar to Step A, discon-
nect All the common control
wires from the common ter-
minal(s) of the controller.
Join these wires to the
White Receiver control wire
using a wire nut. Be sure to
include the common wire
from the Pump Start Relay
with these. Next attach the
Brown Receiver control
wire to the common termi-
nal on the controller.
Step 2. Power Wires (low voltage):
1 2 3 4
Valve
Terminals
To Valves
Common From Valves
White
Yellow*
Valve Controller / Timer
Pump / MV
24 VAC
24 VAC
Black
Red
S
S
C
* Use Green wire (in place of Yellow) if a normally open circuit is required
1 2 3 4
Valve
Terminals
To Valves
Common From Valves
White
Yellow*
Valve Controller / Timer
Pump / MVPump / MV
24 VAC24 VAC
24 VAC24 VAC
Black
Red
SS
SS
CC
* Use Green wire (in place of Yellow) if a normally open circuit is required
Fig. 4
!
1 2 3 4
Valve
Terminals
To Valves
Common From Valves
White
Yellow
Wire Nut
Valve Controller / Timer
Pump / MV
24 VAC
24 VAC
Black
Red
C1 2 3 4
Valve
Terminals
To Valves
Common From Valves
White
Yellow
Wire Nut
Valve Controller / Timer
Pump / MVPump / MV
24 VAC24 VAC
24 VAC24 VAC
Black
Red
CC
Fig. 3
Brown
Brown
1 2 3 4
Valve
Terminals
To Valves
Common From Valves
White
Yellow
Wire Nut
Valve Controller / Timer
Pump / MV
C
24 VAC
24 VAC
Black
Red
Pump
Start
Relay
1 2 3 4
Valve
Terminals
To Valves
Common From Valves
White
Yellow
Wire Nut
Valve Controller / Timer
Pump / MVPump / MV
CC
24 VAC24 VAC
24 VAC24 VAC
Black
Red
Pump
Start
Relay
Pump
Start
Relay
Fig. 5
Brown
Brown) *Use Green wire (in place of Brown) if a normally open circuit is required.
IMPORTANT: Do NOT connect the Receiver directly to 120/240VAC
as this will result in irreversible damage. If you are in doubt, contact a
qualified installer or electrician.
3