EasyManua.ls Logo

Rational 60.72.320 - Page 10

Rational 60.72.320
76 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UV/EH V06 08/2015 - 10 -
- Disconnect unit from mains, on which UV/EH shall
be installed
- Check door of the unit for correct adjustment
- Replace rear screw of the top door holding
plate by stud (item7) and washer. pic. 6
- Carefully place the UV/EH onto the unit. pic. 7
- Fasten UV/EH with screw and washer (item8)
to previous installed stud. pic. 8
- Remove the left side panel of the unit.
4. Installation of the bus cable
- At the rear side of the UV/EH the connection box
with the control pcb is located.(pic. C/D/E/F).
- A bus cable is connected to the control pcb and
guided through the cable gland of the connection
box. An additional cable gland is installed
to the bus cable. pic. 10
- There are knock outs in the bottom of the electric
compartment. Break one of these out. Run the bus
cable of the UV/EH through this knock
out and fix the cable gland to it. pic. 11
- Additionally fix shielding plate (item 11) to
cable gland and connect it to the shield of the
bus cable (cut out insulation of the bus cable)
pic 10
- Connect the bus cable to the unit:
on electric units at a free connector of the
motor control pic. 12
on gas appliances at a free connector of an
ignition box pic. 13
- The cable can be axed to the back of the appli-
ance with the self-adhesive cable clips
(pic.1 item 3) supplied. pic. 14
5. Drain for condensation water.
On the rear side of the UV/EH a drain
connection for condensation water is installed
- Fit the silicone hose (pic 1 item 4) with the hose
clamp (pic 1 item 5) to the elbow. pic. 15
- Put the drain pipe (pic 1 item 6) to the drain
of the unit. pic. 16
- Shorten the silicone (pic 1 item 4) hose to the
desired length and connect it to the drain
pipe (pic 1 item 6). pic. 16
6. Electrical connection of the UV/EH
Danger
Observe local regulations and standards
during installation
Warning
Observe colour coding of the wires. Wrong connec-
tion can cause electric shock
Attention:
Wrong connection can cause damages (e. g. fan
motor)
Colour coding of wires:
yellow/green = earth
blue = neutral
black = Phase
- The UV/EH must be connected to a standard mains
in accordance with the local regulations.
- Before pulling the plug or reconnecting to the power
supply, make sure that the SelfCooking Center or
the Combi Master is switched o to avoid that the
UV/EH starts to run.
- A permanent connection shall be provided for the
UV/EH. On-site installation:
provide accessible all-pole disconnection device
with a minimum of a 3 mm contact gap. If the UV/
EH shall be connected with a plug make sure that it
is accessible
- The UV/EH must be protected on site with a maxi-
mum fuse of 16 A. The UV/EH is fitted with a cable
approx. 2 m in length without plug.
- If the power cord shall be changed, the quality of
the cord must be at least
H05 RN-F 3x1,5 mm
2
In case the power cable must be changed use a
cable that matches your local standards.
The exchange of the power cable may only be car-
ried out by the manufacturer, his service agents or
similar qualified personal
Installation instruction

Related product manuals