3. TROUBLESHOOTING
26
3-1-9 No AC Output Voltage
TROUBLE
CAUSE
REMEDY
No AC output voltage
Engine speed abnormal
Check and adjust
Stator main coil defective
Check and adjust
Brush defective
Check and adjust
Excitation voltage too low
Check and adjust
AVR defective
Check and adjust
Breaker tripped
Reset breakers
Plugging part contacting poor or loosen
Replace the plugging parts or replace.
3-1-10 No DC Output Voltage
TROUBLE
CAUSE
REMEDY
No DC output
voltage
Breaker tripped
Reset breakers
Diode burn
Send to our company repairing station
Wiring connection mistaken or looseness.
Reconnect wiring
Rectification bridge damaged or DC winding
open circuit
Replace the rectification bridge and stator.
3-1-11 Stator Iron Core Overheat
CAUSE
REMEDY
Stator voltage too high operation, and iron core loss
increasing results in iron core overheat.
Adjust generator voltage for keep rated voltage
operation.
Stator winding temperature high, the heat conduct to
the iron core.
If the stator temperature is too high at rated
condition, should lower the generator load.
Rotor exciting current is too big, and rotor winding
temperature too high, heat conduct to the stator iron
core.
Adjust generator load to make the power not out of
the specified valve.
Generator operating with load at low speed, and heat
dispersion condition poor result in iron core heating.
Adjust engine speed for good ventilation.