Do you have a question about the Rayleigh Instruments RI-F300 and is the answer not in the manual?
| Brand | Rayleigh Instruments |
|---|---|
| Model | RI-F300 |
| Category | Measuring Instruments |
| Language | English |
Details display, input, installation category, frequency, and environmental parameters.
Specifies RS485 communication and pulse output characteristics.
Essential steps for valid MID installation: CT ratio setting and sealing.
Parameters lock after 15 minutes in programming mode without return to supplier.
Table showing energy reading resolution based on PT/CT ratios and an example.
Follow safety notifications, symbols, and ensure correct usage; avoid hazards.
Only install by competent personnel due to electric shock risk.
Isolate power, verify connections, use specified cables, and comply with local standards.
Procedure to change CT primary input orientation for load monitoring.
Procedure to verify the CT rotation setting on the meter display.
Description of the 6 dedicated keys for parameter viewing.
Meter returns to default page if no key is pressed for 60 sec.
Shows line-neutral/line-to-line voltages and their harmonics.
Displays current parameters, max demand, and harmonics.
Displays voltage, current, power factor, and frequency for each phase.
Displays power factor for each phase and average PF.
Displays active, reactive, apparent power, and demand values.
Displays various energy parameters (import, export, net) by phase and total.
Details available screens for 1-phase 2-wire systems and default behavior.
Press PF key for 10 sec to display CRC, HW/SW versions, and serial number.
Use 'E' button for 3 seconds to switch between auto and manual page scroll.
EC Type Examination Certificate and tested standards for MID compliance.
Use specific keys for 3 sec to enter/exit the configuration menu.
Use arrow keys for cursor movement and value adjustment.
Use the 'Enter' key to save settings and move to the next page.
Setting password, network selection, CT/PT primary and secondary values.
Configuring Slave ID, Baud Rate, Parity, and Stop Bit.
Configuring backlight, demand intervals, and page sequence.
Setting pulse resolution, duration, and meter reset options.
Shows dimensions and required panel cutout for installation.
Steps for preparing the panel and securing the meter.
Identifies terminals for CT input, RS485, Pulse Output, and Voltage Input/Output.
Only compatible with specified Rayleigh Instruments CTs.
Meter requires Neutral; Voltage output supports daisy-chaining.
Addresses for Password, Slave ID, Baud Rate, Parity, and Stop Bit.
Addresses for Backlight, Auto Mode Pages, and Page Address Sequences.
Addresses for Demand Interval settings and Reset functions.
Formula to calculate addresses for individual harmonic measurements.
Example calculation for finding the address of Voltage V31 14th Harmonic.
Addresses for voltage, current, and frequency readings.
Addresses for active, apparent, reactive power, demand, and energy values.
Addresses for Total Harmonic Distortion, Phase Sequence, and rollover counters.
Describes the semiconductor pulse output and its interface options.
Diagram showing connections for RS485 communication and daisy-chaining.
Recommends terminating resistor and shows example meter displays.
Contact details and website for Rayleigh Instruments Ltd.
Loading...