CONTROL METHODS HeatNet Control V3
Page 30
DHW Method 1 Quick Start Settings
DHW METHOD 1: DHW Heating ONLY Using a DHW MASTER and Member Boiler(s)
Master (DHW Only)
Settings
DHW Use Sensor
HeatNet Address
Master Type
Combustion Air Damper
Yes
Automatic
DHW Only
Off
Inputs
Local/Remote
DHW Sensor
JPS1 Jumper must be cut to service DHW
Local
Yes - Tank
Outputs
Local Pump On
When Boiler Running
Member 2
Settings
HeatNet Address
Combustion Air Damper
2
Off
Inputs
Local/Remote
JPS1 Jumper must be cut to service DHW
Remote
Outputs
Local Pump On
When Boiler Running
Member 3
Settings
HeatNet Address
Combustion Air Damper
3
Off
Inputs
Local/Remote
JPS1 Jumper must be cut to service DHW
Remote
Outputs
Local Pump On
When Boiler Running
Note: The example drawings in this section are simplified. They are meant to illustrate connections to the HeatNet V3 control.
Only major components are illustrated.
The system engineer must ensure additional safeties, piping, maintenance valves, and components meet code requirements and
safe operation.