Figure 10 Typical Primary/Secondary, Low Temperature Piping System (See Notes)
NOTES:
1. Boiler circuit piping must be sized large enough to handle maximum ow through unit.
2. Boiler and pump purging required. Air must be purged from 3-way valve after the boiler is lled. Use purge
valves provided. Purge valve may be located on pump ange. On multiple boiler installations the ow switch
may fail due to trapped air. See manual for procedure.
3. All boilers furnished with factory mounted outlet water temperature gauge.
4. For HeatNet operation, a sensor is required and installation at a minimum of 12" from the primary tee.
Notice: These drawings show suggested piping con guration, valving and are diagrammatic.
Check with local codes and ordinances for speci c requirements.
H-16 REV C