L.P.G. Burner
The L.P.G. burner is a flat steel burner. This burner is supplied with a bag of coarse
vermiculite, spread this thinly (5 to 10mm) over the surface of the burner.
Follow instructions for coal placement as with Natural Gas burner.
Commissioning of the Burner
The mains power supply needs to be connected and turned on. See instructions for
remote control. Press the power on at the remote. The pilot should ignite, it may take
several attempts until air has been purged out and gas is through. Once the pilot has
ignited the burner will light. Check that the flame travels easily across the burner and
that coal placement does not affect ignition. Re- position coals if required.
Ensure that there is no vermiculite touching the Pilot, ignition electrode, or flame
sense electrode. This will cause ignition failure.
Burner Gas pressure
Check burner gas pressure from the test point on the burner supply pipe on the
Natural gas model and on the injector elbow on the L.P.G. model.
See appliance data badge for pressure settings.
Adjustment of the Burner Gas pressure
Adjust the pressure at the gas valve if required. See valve picture
There are two adjustments, High and low setting. These are located at the front of the
valve at the head of the blue solenoid.
High adjustment – This is the outer Brass hexagonal nut
Low Adjustment - This is the inner Red adjustment screw
When adjusting the high setting hold the low adjuster in place otherwise both may
turn.
Fit the front fascia panel
Fit front fascia panel correctly onto fixing screws
Fit side reflectors
Fit side reflectors by tilting on an angle locating base onto fascia panel and then
placing vertical. The return on the reflector then hooks over a securing screw in the
side of the firebox.