5.3 MODULE 3 - DISPLAY AND FRONT PANEL BUTTON
P
ARAMETERS (3-dSP)
PAR
Pro
Front Panel
Display
Select Enable
Display
Update Time
Front Panel
Reset Enable
Programming
Security Code
Zero Display
W/Display
Reset
3-dSP
dSP-t SEL rSt ZErO CodE
Display
Intensity
Level
d-LEVScroL
Display
Scroll
Enable
PARAMETER MENU
1
dSP-t
DISPLAY UPDATE TIME
This parameter sets the display update time in seconds.
1
0.5
2
seconds
The yES selection allows the SEL button to toggle through the enabled
displays.
FRONT PANEL DISPLAY SELECT ENABLE (SEL)
yES
SEL
yES NO
This parameter enables the RST button or user input to zero the input display
value, causing the display reading to be offset.
Note: For this parameter to operate, the RST button or User Input being used
must be set to dSP and the Input value must be displayed. If these conditions are
not met, the display will not zero.
ZERO DISPLAY WITH DISPLAY RESET
NO
ZErO
yES NO
The yES selection allows the display to automatically scroll through the
enabled displays. The scroll rate is every 4 seconds. This parameter only appears
when the MAX or MIN displays are enabled.
DISPLAY SCROLL ENABLE
NO
ScroL
yES NO
The Security Code determines the programming mode and the accessibility
of programming parameters. This code can be used along with the Program
Mode Lock-out (P-Loc) in the User Input Function parameter (Module 1).
Two programming modes are available. Full Programming mode allows all
parameters to be viewed and modified. Quick Programming mode permits only
the Setpoint values to be modified, but allows direct access to these values
without having to enter Full Programming mode.
Programming a Security Code other than 0, requires this code to be entered
at the CodE prompt in order to access Full Programming mode. Depending on the
code value, Quick Programming may be accessible before the CodE prompt
appears (see chart).
PROGRAMMING SECURITY CODE
000 to 999
Enter the desired Display Intensity Level (1-5). The display will actively dim
or brighten as levels are changed.
DISPLAY INTENSITY LEVEL
1 to 5
5
d-LEV
000
CodE
USER INPUT
FUNCTION
USER INPUT
STATE
SECURITY
CODE
MODE WHEN “SEL”
BUTTON IS PRESSED
FULL PROGRAMMING
MODE ACCESS
0
Full Programming Immediate Access
not P-Loc
______
1-99
Quick Programming
After Quick Programming
with correct code entry at
CodE prompt *
100-999
CodE prompt
With correct code entry
at
CodE prompt *
0
Programming Lock No Access
Active
1-99
Quick Programming No Access
P-Loc
100-999
CodE prompt
With correct code entry
at
CodE prompt *
Not Active 0-999
Full Programming Immediate Access
This selection allows the RST button to reset the selected value(s).
FRONT PANEL RESET ENABLE (RST)
dSP
rSt
HI-LO
LO
HI
NO dSP