INSTRUMENTS
Note: Makesurethatthecircuitunderdoesnotincludecomponents
Whichwillbedamagedbythe1000Vapplied.Manynormalcomponents
ofaninstallationarelikelytobedamagediftestedat1000V.Examplesare
powerfactorcorrectioncapacitors,lowvoltagemineralinsulatedcables,
electroniclightdimmers,electronicballastsandstartersforuorescent
lampsetc…
Lock Power on Feature
Forhandsfreeoperationalockpoweronfeatureisincorporatedinthe
presstotestbutton.SettheLOCKbuttontolocktestvoltage,pressingit
again will turn the tester off.
Low Resistance (Continuity) Measurements
1.Settherangeswitchto200Ω•)))Position
2.ConnecttheredtestleadtotheVΩterminalandbacktothe
COMterminal.
3.Connectthetipsofthetestleadstobothendsofthecircuitundertest.
ReadresistanceinΩontheLCD.
4.Whentheimpedanceoncircuitisbelowapproximately40Ω.
Itwillindicatebyacontinuousbeeper.
AC/DC Voltage Measurements
1.SettherangeswitchtoACVorDCVposition
2.Connectredtestleadto“VΩ”terminalandblacktestlead
toterminal“COM”.
3.ConnecttestprodsoftestleadsINPARALLELtothecircuit
beingmeasured.
4.ReadthevoltagevalueonLCD.
w ww . . co m