INSTRUCTION
i
Read this instruction before installation
and wiring of the product
PULSER
Consult documentation in all cases where this symbol
is used, in order to nd out the nature of the potential
hazards and any actions to be taken
1
PULSER
Technical data
Supply voltage 200...415 V AC, 50...60 Hz, 1- or 2-phase,
with automatic voltage adjustment
Power output Up to 16A, min. 1 A. At 230 V, max. output is
3.6 kW and min. output 230 W. At 400 V max.
output will be 6.4 kW and min. output will be
400 W.
Ambient temperature Max. 30°C (Note: PULSER generates 20 W
heating at full load.)
Storage temperature -40...+50°C
P-band 20 K (rapid temperature changes),
1.5 K (slow temperature changes)
I-time 6 min (rapid temperature changes)
Pulse period 60 s.
Indicator Red LED on PULSER, lights up as power is
pulsed to the heater
Mounting Wall
Protection class IP20
Control unit parameters Supply air control: PI function using P-band
20 K and I-time 6 min. Room control: P func-
tion using P-band 1.5 K
Built-in sensor Measurement range 0...30°C
Input external sensor/
setpoint For Regin brand NTC sensors and setpoint
devices, temperature range depends on
measurement range of sensor
Weight 0.3 kg
Dimensions (HxBxD) 153x93x40 cm
Settings
Setpoint 0...30°C
Night set-back 0...10 K
Control principle
PULSER pulses the full load On-Off. PULSER adjusts its mean power
output to the prevailing power demand by proportionally adjusting the ratio
between On-time and Off-time. The pulse period (= the sum of On-time
and Off-time) is xed 60 seconds.
PULSER has zero phase-angle ring to eliminate RFI.
PULSER automatically adjusts its control mode to suit the control object
dynamics.
For rapid temperature changes (i. e. supply air control), PULSER will act
as a PI controller with a proportional band of 20K and a reset time of 6
minutes.
For slow temperature changes (i. e. room control), PULSER will act as a
P controller with a proportional band of 1.5K.
Assembly
Remove the front (the locking screw is located behind the setpoint
knob) and mount PULSER vertically, so that the cooling ange is at its
top. Screws with a maximum head diameter of 5.5mm can be used.
If PULSER is to be used with the internal sensor, mount it approx.
5ft above oor level at a location with a representative temperature.
The air must be able to circulate freely around the PULSER, without
disturbances from doors, furniture, etc.
If PULSER is to be used with an external sensor it may be placed in
any location.
PULSER emits approx. 20W of heat which must be dissipated.
At full load, the maximum ambient temperature is 30°C.
Electrical installation
The installation, which should be proceeded by a fully isolating switch
with a contact gap of at least 3 mm, should be carried out by a quali-
ed technician and in accordance with applicable directives.
K12U34UKGG
Figure 1: Wiring of supply voltage and heater
Terminals 1 and 2: Not polarity sensitive.
Supply voltage: 200 - 415V AC, 50 - 60 Hz with automatic
voltage adjustment.
Maximum current: 16A.
Terminals 3 and 4: Resistive single- or two-phase heater
Maximum load: 3680W at 230V (16A),
6400W at 400V (16A)
Minimum load: 230W at 230V (1A)
400W at 400V (1A)
CAUTION: The cooling ange is live!
1797I
APR 13
EN
Triac controller for proportional control
of electric heating
PULSER is a complete proportional controller for electric heating.
It has automatic voltage adjustment and can be used with either a
built-in sensor or an external sensor. PULSER pulses the whole load
On - Off. The ratio between On-time and Off-time is varied 0 - 100%
to suit the prevailing heat demand. The current is always switched at
zero phase angle to prevent RFI.
PULSER is only intended for control of electric heating: its con-
trol principle makes it unsuitable for control of motors or lighting.
PULSER cannot control 3-phase loads, as one phase is regulated.
Question and Answer IconNeed help?

Do you have a question about the Regin PULSER and is the answer not in the manual?

Regin PULSER Specifications

General IconGeneral
BrandRegin
ModelPULSER
CategoryThermostat
LanguageEnglish

Summary

Product Overview and Functionality

Product Description

PULSER is a proportional controller with automatic voltage adjustment for electric heating, usable with internal or external sensors.

Operational Limitations

Unsuitable for motors/lighting; PULSER cannot control 3-phase loads as only one phase is regulated.

Technical Specifications

Key Technical Data

Details supply voltage, power output, temperature ranges, control parameters, mounting, protection class, and indicators.

Installation and Wiring

Assembly and Mounting

Mount vertically with cooling flange at top. Use appropriate screws and ensure free air circulation around the unit.

Electrical Installation Safety

Installation by qualified technician using a fully isolating switch with a contact gap of at least 3 mm.

Terminal Connections and Load

Connect supply voltage to terminals 1 & 2 (200-415V AC, 16A max) and load to terminals 3 & 4.

Cooling Flange Safety Warning

CAUTION: The cooling flange is live. Handle with care to avoid electrical shock.

Configuration and Operation

Sensor and Setpoint Configuration

Details switch settings for internal/external sensors and setpoints, referencing figures for specific configurations.

Setpoint Range Limiting

Mechanically limit the setpoint range using rings behind the setpoint knob by adjusting blue and red rings.

Night Set-back Function

Describes the wiring for the night set-back function, which provides a potential-free closure for temperature adjustment.

Start-up and Fault Finding

Provides steps for initial checks, resistance measurement, and verifying LED operation during start-up.

Troubleshooting Steps

Offers guidance for troubleshooting issues, including checking sensor wiring and switch settings.