Revision: I-SCE (09-18) PN207697R9
SEPARATED-COMBUSTION,
PACKAGED FURNACE/BLOWER,
MODEL SCE
INSTALLATION/OPERATION/MAINTENANCE
 ⚠ WARNING ⚠ 
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death, or
property damage.
Be sure to read and understand the installation, operation, and service instructions
in this manual.
Improper installation, adjustment, alteration, service, or maintenance can cause serious
injury, death, or property damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of
this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Leave the building immediately.
Immediately call your gas supplier from a phone remote from the building. Follow the
gas suppliers instructions.
If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or
the gas supplier.
DO NOT DESTROY. PLEASE READ CAREFULLY. KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
Supersedes: I-SCE (5-15) PN207697Rev8
TABLE OF CONTENTS
IMPORTANT SAFETY INFORMATION .................................................................. 2
GENERAL INFORMATION ............................................................................ 3
Installation Codes ................................................................................. 3
Special Installations (Aircraft Hangars/Garages) .......................................................... 3
Warranty ........................................................................................ 4
INSTALLATION ..................................................................................... 4
Dimensions ...................................................................................... 4
Uncrating/Unpacking ............................................................................... 5
Clearances ....................................................................................... 6
Location ......................................................................................... 6
Weights ......................................................................................... 6
Suspension ...................................................................................... 6
Mounting ........................................................................................ 7

Table of Contents

Questions and Answers

  • J
    Jessica MarquezAug 5, 2025
    What to do if the Reznor Blower venter motor will not start?
    • E
      Emily RangelAug 5, 2025
      If the venter motor on your Reznor Blower isn't starting, here are a few things you can check: * First, make sure the power to the furnace is on and check the supply fuses or circuit breaker. * Next, verify that there is 24-volt power to the venter relay. Turn up the thermostat and check the control transformer output. Also, check for any loose or improper wire connections. * If power is available and the connections are good, the venter relay, motor, or capacitor might be defective and need replacement.
  • J
    John MartinezAug 9, 2025
    Why is my Reznor Blower motor turning on and off?
    • S
      sarah04Aug 9, 2025
      If your Reznor Blower motor is turning on and off, it could be due to the motor overload device cycling. Verify the motor load against the motor rating plate. If necessary, replace the motor or overload device. Also, if you have a 3-phase motor, ensure it is rotating in the correct direction by interchanging two legs of the supply connections.
  • S
    sarahparkerAug 13, 2025
    What to do if Reznor Blower pilot lights, but the main valve won't open?
    • E
      Eric TurnerAug 13, 2025
      If the pilot light is on but the main valve of your Reznor Blower won't open, try the following: * Ensure the manual valve is open. * Check for defective valve. If 24-volt power is measured at the valve connections and valve remains closed, replace the valve. * Inspect and tighten all wiring connections. * Make sure the flame sensor lead is not grounded and that the insulation or ceramic is not cracked; replace as required. * If all checks indicate no other cause, replace the ignition controller.
  • L
    Linda WilliamsAug 17, 2025
    Why does the Reznor SCE 300 motor cut out on overload?
    • M
      Maria PetersonAug 17, 2025
      If the motor on your Reznor Blower cuts out on overload, it could be due to a few reasons: * The motor pulley may not be properly adjusted. * There might be improper static pressure on the duct system, so adjust the dampers. * Also, check the power supply for low voltage.
  • W
    Wanda McphersonAug 26, 2025
    Why is my Reznor SCE 300 Blower not producing enough heat?
    • L
      Lori DillonAug 26, 2025
      If your Reznor Blower isn't providing sufficient heat, consider the following: * Dirty filters in the blower system can restrict airflow, so clean or replace them. * Limit control cycling can also affect heating performance, so check the air throughput. * Ensure that wiring connections are in accordance with the wiring diagram. * The fan control could be defective and require replacement. * If the blower is set for too low a temperature rise, decrease the blower speed or increase static pressure.
  • K
    kennethparksAug 30, 2025
    What to do if the Reznor Blower motor will not run?
    • M
      Mason KnightAug 30, 2025
      If the motor in your Reznor Blower isn't running, check the following: * Inspect the wiring and connections for any open circuits. * Replace the fan control if it's inoperative. * Ensure that wiring connections are in accordance with the wiring diagram. * Replace the contactor if it is inoperative. * If none of the above steps work, the motor may be defective and require replacement.
  • J
    Joy SmithNov 21, 2025
    Why won't the pilot light on my Reznor Blower even with the venter operating?
    • K
      Kaitlin GilmoreNov 21, 2025
      If the pilot light on your Reznor Blower won't light even when the venter is operating, consider these potential causes: * Ensure the manual valve is open. * Bleed the gas line to remove any air. * Clean the pilot orifice with compressed air or solvent to remove any dirt. * Check for kinked pilot tubing and replace if necessary. * If 24-volt power is available at the pilot valve and it doesn't open, replace the valve. * Make sure all wire connections are solid. * Ensure that 24-volt power is available by checking for transformer failure. * Maintain the spark gap at 0.100 inch. * Replace the spark cable if it's shorted to ground. * Replace the pilot if the ceramic spark electrode is cracked or grounded. * Ensure all panels are in place and tightly secured to prevent d...

Summary

Important Safety Information

General Information

Installation Codes

Details requirements for installing units in accordance with local and national codes.

Installation

Uncrating;Unpacking

Instructions for safely removing the unit from its packaging and checking for shipping damage.

Clearances

Specifies minimum clearance distances to combustible materials for safe installation.

Venting and Combustion Air

Specific Venting Requirements: Piping

Details requirements for vent pipe and combustion air pipe, including type, length, and diameter.

Specific Venting Requirements: Joints and Sealing

Provides step-by-step instructions for sealing various pipe joints in the venting system.

Specific Venting Requirements: Concentric Adapter Box

Details the concentric adapter box, its function, and installation dependencies.

Specific Venting Requirements: Concentric Adapter Box Pipe Connections

Explains the required pipe diameters and connections for the concentric adapter box.

Venting Options

Horizontal Vent Terminal;Combustion Air Package Kit (Option CC6)

Details the components and installation instructions for the horizontal venting option.

Vertical Vent Terminal;Combustion Air Package Kit (Option CC2)

Details the components and installation instructions for the vertical venting option.

Gas Piping and Pressures

Pressure Testing Gas Supply Piping

Describes procedures for safely testing gas supply piping for leaks and pressure.

Manifold or Orifice (Valve Outlet) Pressure Settings

Details manifold gas pressure settings and warnings for natural gas and propane.

Electrical Supply and Connections

Combustion Air Proving Switch

Explains the function and settings of the combustion air proving switch for safe operation.

Operating Valve

Describes the function and safety aspects of the unit's combination gas operating valve.

Installation and Startup Checklists

Pre-Startup Checklist

A checklist of critical items to verify before initiating unit startup procedures.

Startup Checklist

Steps to follow for proper furnace startup, including safety checks and operational sequences.

Post-Startup Checklist

Procedures for verifying correct operation after startup, including flame observation and pressure checks.

Service and Maintenance

Operating Gas Valve Maintenance

Annual checks for the combination gas valve to ensure it shuts off gas flow completely.

Troubleshooting

Reznor SCE 300 Specifications

General IconGeneral
ModelSCE 300
Efficiency80%
Heating Capacity300, 000 BTU/hr
Phase1
Gas TypeNatural Gas or Propane