SEPARATED-COMBUSTION,
PACKAGED FURNACE/BLOWER,
MODEL SCE
INSTALLATION/OPERATION/MAINTENANCE
 ⚠ WARNING ⚠ 
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death, or
property damage.
Be sure to read and understand the installation, operation, and service instructions
in this manual.
Improper installation, adjustment, alteration, service, or maintenance can cause serious
injury, death, or property damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of
this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Leave the building immediately.
Immediately call your gas supplier from a phone remote from the building. Follow the
gas suppliers instructions.
If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or
the gas supplier.
DO NOT DESTROY. PLEASE READ CAREFULLY. KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
Supersedes: I-SCE (5-15) PN207697Rev8
TABLE OF CONTENTS
IMPORTANT SAFETY INFORMATION .................................................................. 2
GENERAL INFORMATION ............................................................................ 3
Installation Codes ................................................................................. 3
Special Installations (Aircraft Hangars/Garages) .......................................................... 3
Warranty ........................................................................................ 4
INSTALLATION ..................................................................................... 4
Dimensions ...................................................................................... 4
Uncrating/Unpacking ............................................................................... 5
Clearances ....................................................................................... 6
Location ......................................................................................... 6
Weights ......................................................................................... 6
Suspension ...................................................................................... 6
Mounting ........................................................................................ 7

Table of Contents

Questions and Answers

  • D
    Deborah BlevinsAug 5, 2025
    What to do if the Reznor SCE 200 Blower venter motor will not start?
    • A
      Amanda FergusonAug 5, 2025
      If the venter motor on your Reznor Blower isn't starting, here are a few things you can check: * First, make sure the power to the furnace is on and check the supply fuses or circuit breaker. * Next, verify that there is 24-volt power to the venter relay. Turn up the thermostat and check the control transformer output. Also, check for any loose or improper wire connections. * If power is available and the connections are good, the venter relay, motor, or capacitor might be defective and need replacement.
  • M
    marknicholsAug 9, 2025
    Why is my Reznor SCE 200 motor turning on and off?
    • K
      kingbreannaAug 10, 2025
      If your Reznor Blower motor is turning on and off, it could be due to the motor overload device cycling. Verify the motor load against the motor rating plate. If necessary, replace the motor or overload device. Also, if you have a 3-phase motor, ensure it is rotating in the correct direction by interchanging two legs of the supply connections.
  • J
    Jodi CopelandAug 13, 2025
    What to do if Reznor SCE 200 pilot lights, but the main valve won't open?
    • T
      Tammie SheppardAug 13, 2025
      If the pilot light is on but the main valve of your Reznor Blower won't open, try the following: * Ensure the manual valve is open. * Check for defective valve. If 24-volt power is measured at the valve connections and valve remains closed, replace the valve. * Inspect and tighten all wiring connections. * Make sure the flame sensor lead is not grounded and that the insulation or ceramic is not cracked; replace as required. * If all checks indicate no other cause, replace the ignition controller.
  • C
    christopher05Aug 18, 2025
    Why does the Reznor SCE 200 motor cut out on overload?
    • C
      Colleen AguilarAug 18, 2025
      If the motor on your Reznor Blower cuts out on overload, it could be due to a few reasons: * The motor pulley may not be properly adjusted. * There might be improper static pressure on the duct system, so adjust the dampers. * Also, check the power supply for low voltage.
  • J
    Jennifer GarciaAug 27, 2025
    Why is my Reznor SCE 200 Blower not producing enough heat?
    • M
      marieorozcoAug 27, 2025
      If your Reznor Blower isn't providing sufficient heat, consider the following: * Dirty filters in the blower system can restrict airflow, so clean or replace them. * Limit control cycling can also affect heating performance, so check the air throughput. * Ensure that wiring connections are in accordance with the wiring diagram. * The fan control could be defective and require replacement. * If the blower is set for too low a temperature rise, decrease the blower speed or increase static pressure.
  • S
    Sean ChenAug 30, 2025
    What to do if the Reznor SCE 200 motor will not run?
    • S
      scottabbottAug 30, 2025
      If the motor in your Reznor Blower isn't running, check the following: * Inspect the wiring and connections for any open circuits. * Replace the fan control if it's inoperative. * Ensure that wiring connections are in accordance with the wiring diagram. * Replace the contactor if it is inoperative. * If none of the above steps work, the motor may be defective and require replacement.
  • J
    joanna45Nov 21, 2025
    Why won't the pilot light on my Reznor SCE 200 Blower even with the venter operating?
    • M
      Matthew MartinezNov 21, 2025
      If the pilot light on your Reznor Blower won't light even when the venter is operating, consider these potential causes: * Ensure the manual valve is open. * Bleed the gas line to remove any air. * Clean the pilot orifice with compressed air or solvent to remove any dirt. * Check for kinked pilot tubing and replace if necessary. * If 24-volt power is available at the pilot valve and it doesn't open, replace the valve. * Make sure all wire connections are solid. * Ensure that 24-volt power is available by checking for transformer failure. * Maintain the spark gap at 0.100 inch. * Replace the spark cable if it's shorted to ground. * Replace the pilot if the ceramic spark electrode is cracked or grounded. * Ensure all panels are in place and tightly secured to prevent d...

Summary

Safety and General Information

General Safety and Gas Leak Procedures

Essential safety warnings, including what to do if gas is detected.

Unit Overview and Installation Codes

Unit description, certification, and compliance with installation codes and standards.

Installation Procedures

Unit Dimensions, Clearances, and Weight

Physical specifications and spatial requirements for safe unit installation.

Unpacking, Mounting, and Suspension

Procedures for unpacking, securing, and hanging the unit for proper operation.

Ductwork and Venting Connections

Guidelines for connecting ducts and installing vent/combustion air systems.

Venting and Combustion Air Systems

Details requirements for installing combustion air and vent systems, including options.

Horizontal Venting Option (CC6)

Instructions for installing the horizontal vent terminal and combustion air package kit.

Vertical Venting Option (CC2)

Instructions for installing the vertical vent terminal and combustion air package kit.

Gas Piping and Pressure Requirements

Specifications for gas supply connections, pressure testing, and manifold pressure.

Electrical Supply and Wiring

Guidelines for electrical connections, including wire sizes and safety precautions.

Unit Controls and Operation

Thermostat, Blower, and Gas Valve Control

Settings and operation of thermostats, blower fan, and gas valves.

Optional Operation Modes

Details on two-stage operation and electronic modulation features.

System Components and Maintenance

Pilot, Ignition, and Burner Systems

Maintenance and specifications for pilot, ignition, and burner assemblies.

Optional Equipment and Features

Information on optional drains, dampers, filters, and dirty filter switch.

Startup, Service, and Troubleshooting

Installation and Startup Checklists

Steps for pre-startup, startup, and post-startup verification.

Routine Maintenance Procedures

Guidelines for servicing gas valves, vent systems, and burner racks.

Troubleshooting Common Issues

A guide to diagnosing and resolving common operational problems and symptoms.