How to troubleshoot Reznor SDH Air Handlers venter motor that won't start?
- SSteve WongAug 11, 2025
If the venter motor in your Reznor Air Handlers unit isn't starting, several issues could be at play. First, ensure the unit has power by checking the supply fuses or circuit breaker. Then, verify power is reaching the venter motor by examining connections at the burner relay and/or venter motor terminals. If those are fine, the integrated burner relay or the venter motor itself might be defective and need replacement. Also, check if fuse (F3.1) or fuse burner relay are blown and replace them if needed. Try resetting LC3 or pushing the reset button. Lastly, make sure the thermostat is set above room temperature.