PRE-ENGINEERED VENTILATION AIR HANDLER
Centrifugal Blown, Forced Convection Appliances with
Automatic Ignition and Fanned Flues for use as Multiple
Type B & C Appliances
INDOOR system
SDH range
OUTDOOR system
RDH range
Applies to
Belarus, Bulgaria, China, Czech Republic, Croatia, Cyprus, Denmark, Estonia, Finland, Greece,
Hungary, Iceland, Latvia, Lithuania, Montenegro, New Zealand, Norway, Poland, Portugal, Romania,
Russian Federation, Serbia, Slovakia, Slovenia, Spain, Sweden, Turkey, Ukraine
INSTALLATION
COMMISSIONING
SERVICING
These appliances meet the following EC Directives
DIR 2009/142/EC:GAD
DIR 2004/108/EC:EMC
DIR 2006/42/EC:MD
DIR 2006/95/EC:LVD
Please read this document carefully before commencing the installation and leave it with the
user or attached to the appliance or gas service meter after installation!
Subject to modifications
Reznor Menen J.&M. Sabbestraat 130, B 8930
Tel.: +32 56/52 95 11 Fax : +32 56/52 95 33

Questions and Answers

  • E
    Erin SerranoAug 9, 2025
    How to troubleshoot Reznor Air Handlers venter motor that won't start?
    • K
      Kathleen JohnsonAug 9, 2025
      If the venter motor in your Reznor Air Handlers unit isn't starting, several issues could be at play. First, ensure the unit has power by checking the supply fuses or circuit breaker. Then, verify power is reaching the venter motor by examining connections at the burner relay and/or venter motor terminals. If those are fine, the integrated burner relay or the venter motor itself might be defective and need replacement. Also, check if fuse (F3.1) or fuse burner relay are blown and replace them if needed. Try resetting LC3 or pushing the reset button. Lastly, make sure the thermostat is set above room temperature.
  • M
    Michelle RiosAug 15, 2025
    What to do if Reznor RDH burner will not light?
    • B
      brittany67Aug 15, 2025
      If the burner in your Reznor Air Handlers isn't lighting, start by checking the voltage on the main valve during the ignition period and inspect the connectors on both the main gas valve and burner relay. Ensure all wire connections are solid and maintain a 3 mm spark gap. If the spark cable is shorted or the ceramic spark electrode is cracked, replace them. Verify the burner relay and the unit are properly grounded (earthed) and phased (L1 to hot lead, L2 to neutral). If voltage is available to the burner relay and all other causes have been eliminated, replace it. Also, confirm the unit is properly vented, remove any obstructions, and replace any faulty tubing or the pressure switch related to the combustion air pressure switch.
  • J
    Jackie BensonAug 20, 2025
    Why does Reznor Air Handlers burner cycle on and off?
    • J
      Jennifer QuinnAug 21, 2025
      If the burner in your Reznor Air Handlers cycles on and off, ensure the gas supply pressure is correct: 15 mbar for natural gas (UK only) or 37 mbar for propane gas. Check the burner relay ground wire connection. If (220/240) volts is available to the burner relay and all other causes have been eliminated, replace it. Make sure the flame sensor lead isn't grounded, and the insulation or ceramic isn't cracked; replace as needed. If the ceramic at the sensor is cracked, replace the sensor. Verify and correct the polarity by reversing line voltage wires to terminal block connections if necessary.
  • B
    Brandy ChenAug 27, 2025
    How to fix Reznor Air Handlers fan motor that will not run?
    • J
      Joseph CamachoAug 27, 2025
      If the fan motor in your Reznor Air Handlers won't run, check the wiring and connections for any open circuits. If the wiring is intact, the fan time delay relay may be defective and require replacement. If the issue persists, the motor itself may be defective, necessitating replacement of the blower and motor.
  • D
    dkimSep 1, 2025
    Why does Reznor RDH fan or venter motor turns on and off during burner operation?
    • B
      Brent KaneSep 1, 2025
      If the fan or venter motor in your Reznor Air Handlers turns on and off while the burner is operating, the motor's internal thermal protection device may be cycling. Check the motor load against the motor rating plate, and replace the motor if needed.

Summary

Location & Installation

SDH Model Location and Installation

Optimal placement, clearances, and securing requirements for SDH units.

RDH Model Location and Installation

Outdoor placement guidelines, security, space, and structural support for RDH units.

Gas Connection

Electrical Connection

Electrical Supply & Connections

Guidelines for electrical installation, wiring, and safety precautions, adhering to IEE regulations.

Wiring Connections on Terminal Board

Diagram and notes for electrical connections on the terminal board, including power supply and controls.

Commissioning, Lighting and Operation

Commissioning Procedures

Steps for initial checks, safety procedures, and startup before operating the air heater.

Ignition System

Explanation of the ignition sequence, burner operation, and safety lockout mechanisms.

Burner Gas Pressure Adjustment

Procedure for checking and adjusting burner gas pressure for optimal performance.

Two Stage Burners Setting & Adjustment

Gas Conversion

Maintenance & Service

Troubleshooting

User Instructions

To Light the Heater

Step-by-step instructions for lighting the air heater, including safety checks and thermostat settings.

Reznor RDH Series Specifications

General IconGeneral
BrandReznor
ModelRDH Series
CategoryAir Handlers
LanguageEnglish