2 Rheem Heating, Cooling and Water Heating
Model Number Identification
13 A J M 18
NOMINAL COOLING CAPACITY
18 = 18,000 BTU/HR [5.28 kW]
24 = 24,000 BTU/HR [7.03 kW]
30 = 30,000 BTU/HR [8.79 kW]
36 = 36,000 BTU/HR [10.55 kW]
42 = 42,000 BTU/HR [12.31 kW]
48 = 48,000 BTU/HR [14.07 kW]
60 = 60,000 BTU/HR [17.58 kW]
A 01
13 SEER A = AIR CONDITIONER VOLTAGE
J = 208-230
SINGLE PHASE
DESIGN
SERIES
M = 2ND
DESIGN R-410A
CABINET
A = FULL METAL JACKET
RHEEM
VALUE
SERIES
Model Numbers
80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Sound
Rating
dB
Indoor
CFM [L/s]
Outdoor
Unit
13AJM
Indoor
Coil and/or
Air Handler
Total
Capacity
BTU/H [kW]
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
EER SEER
18
RCFL-H*2417
19,100 [5.6] 14,450 [4.2] 4,650 [1.4] 11.40 13.00 74 675 [319]
RHAL-FR18P 19,400 [5.7] 14,400 [4.2] 5,000 [1.5] 11.50 13.00 74 600 [283]
RHBL-FR24T 19,400 [5.7] 14,400 [4.2] 5,000 [1.5] 12.00 14.00 74 600 [283]
RCFL-A*2414 19,100 [5.6] 14,450 [4.2] 4,650 [1.4] 11.40 13.00 74 675 [319]
RCFL-A*2417 19,100 [5.6] 14,450 [4.2] 4,650 [1.4] 11.40 13.00 74 675 [319]
RCFL-A*2417 (RGFD-06?MCK?) 19,200 [5.6] 14,300 [4.2] 4,900 [1.4] 12.65 14.00 74 600 [283]
RCFL-A*2417 (RGFD-07?MCK?) 19,200 [5.6] 14,300 [4.2] 4,900 [1.4] 12.65 14.00 74 600 [283]
RCFL-A*2417 (RGFE-06?MCK?) 19,100 [5.6] 14,150 [4.1] 4,950 [1.5] 12.00 14.50 74 575 [271]
RCFL-A*2417 (RGFE-07?MCK?) 19,200 [5.6] 14,300 [4.2] 4,900 [1.4] 12.00 14.50 74 600 [283]
RCFL-A*2417 (RGGD-06?MCK?) 19,300 [5.7] 14,350 [4.2] 4,950 [1.5] 12.80 14.50 74 600 [283]
RCFL-A*2417 (RGGD-07?MCK?) 19,400 [5.7] 14,500 [4.2] 4,900 [1.4] 12.80 14.50 74 625 [295]
RCFL-A*2417 (RGGE-06?MCK?) 19,400 [5.7] 14,550 [4.3] 4,850 [1.4] 12.00 14.50 74 625 [295]
RCFL-A*2417 (RGGE-07?MCK?) 19,100 [5.6] 14,150 [4.1] 4,950 [1.5] 12.00 14.50 74 575 [271]
RCFL-A*2417 (RGLE-07?AMK?) 19,300 [5.7] 14,400 [4.2] 4,900 [1.4] 12.00 14.50 74 600 [283]
RCFL-A*2417 (RGLR-07?AMK?) 19,300 [5.7] 14,350 [4.2] 4,950 [1.5] 12.85 14.50 74 600 [283]
RCFL-A*2417 (RGLT-07?AME?) 19,700 [5.8] 14,900 [4.4] 4,800 [1.4] 12.00 14.50 74 675 [319]
RCFL-A*2417 (RGPE-05?BMK?) 19,100 [5.6] 14,150 [4.1] 4,950 [1.5] 12.00 14.50 74 575 [271]
RCFL-A*2417 (RGPE-07?AMK?) 19,400 [5.7] 14,550 [4.3] 4,850 [1.4] 12.00 14.50 74 625 [295]
RCFL-A*2417 (RGPR-05?BMK?) 19,200 [5.6] 14,300 [4.2] 4,900 [1.4] 12.55 14.00 74 600 [283]
RCFL-A*2417 (RGPR-07?AMK?) 19,300 [5.7] 14,350 [4.2] 4,950 [1.5] 12.80 14.50 74 600 [283]
RCFL-A*2417 (RGPT-05?BMK?) 19,600 [5.7] 14,800 [4.3] 4,800 [1.4] 12.00 14.50 74 650 [307]
RCFL-A*2417 (RGPT-07?AME?) 19,400 [5.7] 14,500 [4.2] 4,900 [1.4] 12.00 14.50 74 625 [295]
RCFL-A*2417 (RGRM-04?MAE?) 19,100 [5.6] 14,150 [4.1] 4,950 [1.5] 12.60 14.00 74 575 [271]
RCFL-A*2417 (RGRM-06?MAE?) 19,200 [5.6] 14,300 [4.2] 4,900 [1.4] 12.70 14.50 74 600 [283]
RCFL-A*2417 (RGRM-07?MAE?) 19,300 [5.7] 14,450 [4.2] 4,850 [1.4] 12.50 14.00 74 625 [295]
RCFL-A*2417 (RGTM-06?MAE?) 19,300 [5.7] 14,450 [4.2] 4,850 [1.4] 12.00 14.50 74 625 [295]
ROCA-070E03 (RCFL-A*2417) 19,300 [5.7] 14,350 [4.2] 4,950 [1.5] 12.00 14.50 74 600 [283]
ROLA-070E03 (RCFL-A*2417) 19,200 [5.6] 14,300 [4.2] 4,900 [1.4] 11.50 14.00 74 600 [283]
RCFL-H*2414 19,100 [5.6] 14,450 [4.2] 4,650 [1.4] 11.40 13.00 74 675 [319]
RCFL-H*2417 (RGFD-06?MCK?) 19,200 [5.6] 14,300 [4.2] 4,900 [1.4] 12.65 14.00 74 600 [283]
RCFL-H*2417 (RGFD-07?MCK?) 19,200 [5.6] 14,300 [4.2] 4,900 [1.4] 12.65 14.00 74 600 [283]
RCFL-H*2417 (RGFE-06?MCK?) 19,100 [5.6] 14,150 [4.1] 4,950 [1.5] 12.00 14.50 74 575 [271]
RCFL-H*2417 (RGFE-07?MCK?) 19,200 [5.6] 14,300 [4.2] 4,900 [1.4] 12.00 14.50 74 600 [283]
RCFL-H*2417 (RGGD-06?MCK?) 19,300 [5.7] 14,350 [4.2] 4,950 [1.5] 12.80 14.50 74 600 [283]
RCFL-H*2417 (RGGD-07?MCK?) 19,400 [5.7] 14,500 [4.2] 4,900 [1.4] 12.80 14.50 74 625 [295]
RCFL-H*2417 (RGGE-06?MCK?) 19,400 [5.7] 14,550 [4.3] 4,850 [1.4] 12.00 14.50 74 625 [295]
RCFL-H*2417 (RGGE-07?MCK?) 19,100 [5.6] 14,150 [4.1] 4,950 [1.5] 12.00 14.50 74 575 [271]
RCFL-H*2417 (RGJD-06?MCK?) 19,300 [5.7] 14,350 [4.2] 4,950 [1.5] 12.80 14.50 74 600 [283]
RCFL-H*2417 (RGJD-07?MCK?) 19,400 [5.7] 14,500 [4.2] 4,900 [1.4] 12.80 14.50 74 625 [295]
RCFL-H*2417 (RGJF-06?MCK?) 19,400 [5.7] 14,550 [4.3] 4,850 [1.4] 12.00 14.50 74 625 [295]
RCFL-H*2417 (RGJF-07?MCK?) 19,100 [5.6] 14,150 [4.1] 4,950 [1.5] 12.00 14.50 74 575 [271]
RCFL-H*2417 (RGLE-07?AMK?) 19,300 [5.7] 14,400 [4.2] 4,900 [1.4] 12.00 14.50 74 600 [283]
Rev.
6/30/10
Performance Data @ AHRI Standard ConditionsCooling
Highest sales volume tested combination required by D.O.E. test procedures. [ ] Designates Metric Conversions