Rheem Manufacturing Company 7
BLOWER PERFORMANCE DATAUPFLOW/HORIZONTAL MODELS
MODEL RGPL-
BLOWER SIZE
(D X W)
INCHES [mm]
ECM
MOTOR H.P.
[W]
BLOWER
SPEED
CFM [L/s] AIR DELIVERY
EXTERNAL STATIC PRESSURE
INCHES WATER COLUMN [kPa]
12
11 x 10
[279 x 254]
1
[746]
HIGH
MED-HI
MED
LOW
2000 [944]
1600 [755]
1400 [661]
1200 [566]
.1 [.025]–.5 [.12]
05
11 x 7
[279 x 178]
3/4
[559]
HIGH
MED-HI
MED
LOW
1200 [566]
1000 [472]
800 [378]
600 [283]
07
11 x 10
[279 x 254]
1/2
[373]
HIGH
MED-HI
MED
LOW
1200 [566]
1000 [472]
800 [378]
600 [283]
10
11 x 10
[279 x 254]
1
[746]
HIGH
MED-HI
MED
LOW
2000 [944]
1600 [755]
1400 [661]
1200 [566]
07
11 x 10
[279 x 254]
3/4
[559]
HIGH
MED-HI
MED
LOW
1600 [755]
1400 [661]
1200 [566]
1000 [472]
Note: See Form Number C11-206 for MultiFlex
®
coil data.