Rheem RH1P2417STANJA - 3.13.4 COPPER WIRE SIZE - AWG. (3% VOLTAGE DROP)

Rheem RH1P2417STANJA
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1817S 1/5 1075 2 2.3 3.0 15
2417S 1/5 1075 2 3.8 5.0 15
3017S
115 1 60
1/4 1075 2 4.7 6.0 15
3617S 1/3 1075 2 6.1 8.0 15
4221S 1/2 1075 2 7.9 10.0 15
4821S 3/4 1075 2 8.4 11.0 15
1817S 1/5 1075 2 1.7 3.0 15
2417S 1/5 1075 2 1.7 3.0 15
3017S
208/240 1 & 3 60
1/4 1075 2 2.5 4.0 15
3617S/3621S 1/3 1075 2 2.5 4.0 15
4221S 1/2 1075 2 5.2 7.0 15
4821S/4824S 3/4 1075 2 5.2 7.0 15
6024S 3/4 1075 2 5.2 7.0 15
3617S 1/3 1075 2 1.4 2.0 15
4221S
480 3 60
1/2 1075 2 2.2 3.0 15
4821S/4824S 3/4 1075 2 2.2 3.0 15
6024S 3/4 1075 2 2.2 3.0 15
23
S
U
P
P
L
Y
W
I
R
E
L
E
N
G
T
H
F
E
E
T
SUPPLY CIRCUIT AMPACITY
NOTE: WIRE BASED ON COPPER CONDUCTORS 75°C MINIMUM RATING.
FOR MORE THAN 3 CONDUCTORS IN A RACEWAY OR CABLE, SEE
N.E.C. FOR DERATING THE AMPACITY OF EACH CONDUCTOR.
12
12
14
14
15
10
10
12
12
20
8
10
10
10
25
8
10
10
10
30
8
8
8
8
35
6
8
8
8
40
6
6
8
8
45
6
6
6
6
50
4
6
6
6
60
4
4
4
4
70
3
4
4
4
80
3
3
3
3
90
2
3
3
3
100
2
2
2
2
110
1
1
1
1
125
0
0
0
0
150
00
00
00
00
175
3.13.4 COPPER WIRE SIZE - AWG. (3% VOLTAGE DROP)
200 [61]
150 [46]
100 [30]
50 [15]
PHASE* HP
MODEL
(-)H1P
VOLTAGE HERTZ RPM SPEEDS
MOTOR
AMPS
MINIMUM
CIRCUIT
AMPACITY
MAXIMUM
OVERCURRENT
PROTECTION
3.13.5.1 ELECTRICAL DATA – BLOWER MOTOR ONLY – WITHOUT ELECTRIC HEAT: (-)H1P
*Blower motors are all single phase motors.
2417S 1/3 300-1100 4 4.8 6 15
3617S/3621M/3621H
115
1
60
1/2 300-1100 4 6.8 9 15
4821S/4821M/4824S 3/4 300-1100 4 9.3 12 15
6021S/6024S 3/4 300-1100 4 9.3 12 15
2417S 1/3 300-1100 4 1.6 2 15
3617S/3621M/3621H
208/240
1 & 3
60
1/2 300-1100 4 2.8 4 15
4821S/4821M 3/4 300-1100 4 4.0 5 15
6021S/6024S/4824S 3/4 300-1100 4 4.6 6 15
3617S 1/2 300-1100 4 2.1 4.0 15
4821S/4824S 480 3 60 3/4 300-1100 4 3.2 4.0 15
6021S/6024S 3/4 300-1100 4 3.2 4.0 15
PHASE*
MODEL
(-)H1T
VOLTAGE HERTZ HP RPM SPEEDS
MOTOR
AMPS
MINIMUM
CIRCUIT
AMPACITY
MAXIMUM
OVERCURRENT
PROTECTION
3.13.5.2 ELECTRICAL DATA – BLOWER MOTOR ONLY – WITHOUT ELECTRIC HEAT: (-)H1T
Supply circuit power wiring must be 75°C minimum copper conductors only. See
Electrical Data in Sections 3.13.5 and 3.13.6 for ampacity, wire size and circuit pro-
tector requirement. Supply circuit protective devices may be either fuses or “HACR”
type circuit breakers.
Field power wiring may be connected to either the right, left side or top. Three
7
/8, 1
3
/3
2
”,
1
3
1
/3
2
” dia. concentric knockouts are provided for connection of power wiring to unit.
Field power wiring is to be connected to the power terminal block in unit control com-
partment.
For units equipped with an electric heater kit, field power wiring is to be connected to
the heater kit breaker, terminal block, or pullout disconnect terminals and the power
wiring pigtail from the heater kit is to be connected to the unit power terminal block in
the unit control compartment. Refer to installation instructions provided with the
heater kit for additional details.