3.13.6.2 ELECTRICAL DATA – WITH ELECTRIC HEAT: (-)H1T - continued
7.2/9.6 3/60 3-3.2 MULTIPLE CKT 1 20.0/23.1 4.6 31/35 35/35
RXBH-24A20C
7.2/9.6 3/60 3-3.2 MULTIPLE CKT 2 20.0/23.1 0 25/29 25/30
4824S RXBH-24A25C* 18.0/24.0 3/60 6-4.0 SINGLE 50.0/57.8 4.6 69/78 70/80
6021S 9.0/12.0 3/60 3-4.0 MULTIPLE CKT 1 25.0/28.9 4.6 37/42 40/45
6024S
RXBH-24A25C
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 2 25.0/28.9 0 32/37 35/40
RXBH-24A30C* 21.6/28.8 3/60 6-4.8 SINGLE 60.0/69.4 4.6 81/93 90/100
RXBH-24A30C
10.8/14.4 3/60 3-4.8 MULTIPLE CKT 1 30.0/34.7 4.6 44/50 45/50
(6024S only)
10.8/14.4 3/60 3-4.8 MULTIPLE CKT 2 30.0/34.7 0 38/44 40/45
RXBH-24A07D 7.2 3/60 3-2.4 SINGLE 8.7 3.2 15 15
RXBH-24A10D 9.6 3/60 3-3.2 SINGLE 11.6 3.2 19 20
4824S RXBH-24A15D 14.4 3/60 3-4.8 SINGLE 17.3 3.2 26 30
6021S RXBH-24A18D 17.0 3/60 6-2.84 SINGLE 20.4 3.2 30 30
6024S RXBH-24A20D 19.2 3/60 6-3.2 SINGLE 23.2 3.2 33 35
RXBH-24A25D 24.0 3/60 6-4.0 SINGLE 28.8 3.2 40 40
RXBH-24A30D
28.8 3/60 6-4.8 SINGLE 34.6 3.2 48 50
(6024S only)
? Heater Kit Connection Type  A=Breaker  B=Terminal Block  C=Disconnect Pullout
*Values only. No single point kit available.
NOTES:
Electric heater BTUH - (heater watts + motor watts) x 3.412 (see airflow table for motor watts.)
Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
Motor load is included in single circuit or circuit 1 of multiple circuits.
Heater loads are balanced on 3 phase models with 3 or 6 heating elements only.
Electric heater kits are not permitted for use with 115 volt air-handlers (A voltage).
J Voltage (208/240V) single phase air-handlers are designed to be used with single or three phase 208/240V electric heaters. To connect 3
phase power to the air handler terminal block, bring only two leads to terminal block, cap, insulate, and fully secure the third lead.
Do not install 480V electric heaters in 208/240V air-handlers.
Do not install 208/240V electric heaters in 480V air-handlers.
If the heater kit is listed under both single and multiple circuits, the heater kit is shipped from factory as multiple circuits. For single phase appli-
cations, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. See Section 6.2 for details.
AIR HANDLER
MODEL
(-)H1T
HEATER
MODEL
NO.
HEATER
KW
(208/240V)
(480V)
PH/HZ
NO.
ELEMENTS
- KW PER
TYPE SUPPLY
CIRCUIT
SINGLE CIRCUIT
MULTIPLE CIRCUIT
HEATER
AMPS
MOTOR
AMPS
MINIMUM
CIRCUIT
AMPACITY
MAXIMUM
OVERCURRENT
PROTECTION