29
9.1 AIRFLOW PERFORMANCE DATA
10.0 SEQUENCE OF OPERATION
10.1 COOLING (cooling only or heat pump)
In a serial communicating network:
When the thermostat “calls for cooling,” a cooling command is sent via the serial net-
work to the air handler and outdoor unit.
Using conventional 24VAC thermostat wiring:
When the thermostat “calls for cooling,” the circuit between R and Y is completed.
A “call for cooling” causes:
1) The blower to start.
2) The compressor relay to close energizing the compressor.
3) The outdoor fan motor to start.
10.2 HEATING (electric heat only)
In a serial communicating network:
When the thermostat “calls for heat,” a heating command is sent via the serial net-
work to the air handler.
Using conventional 24VAC thermostat wiring:
When the thermostat “calls for heat,” the circuit between R and W is completed.
A “call for heat” causes:
1) The heater sequencer (HR1) energizes.
2) A timed delay begins.
3) The indoor blower motor (IBM) starts.
4) The heating elements (HE) energize.
10.3 DEFROST
For sequence of operation for defrost controls, see outdoor heat pump installation
instructions.
10.4 EMERGENCY HEAT (Heating of Heat Pump)
If selector switch on thermostat is set to the emergency heat position, the heat pump
will be locked out of the heating circuit, and all heating will be electric heat.
Size
Motor HP
Thermostat
Input
0.1 0.2 0.3 0.40.50.60.70.8 0.9 1.0
550 575 600 600 625 625625600575550
455 540 620 695 760 8258859409851030
40557085105 120135150170185
775 775 775 800 800 825825825825825
540 615 685 750 810 870 925 975 1020 1065
70 90 115 135 160 180205225250270
875 900 900 900 900 900900900900875
570 645 715 775 835 890 945 990 1030 1070
90 110 135 155 180 200220240265285
1175 1200 1200 1200 122512251200 1200 1200 1200
700 760 820 875 925 9701015 1055 1095 1125
180 205 235 265 290 320345370400425
1200 1175 1175 1200 122512251200 1200 1200 1200
535 595 650 700 750 800840880915950
130 160 190 220 250 280305335365390
1625 1650 1650 1650 167516751675 1650 1650 1625
635 690 745 795 840 8809159509801005
245 295 340 385 425 465500535565590
1375 1375 1375 1375 137513751375 1350 1350 1350
575 630 685 735 780 825865905945980
160 185 215 245 275 305335365395430
1650 1675 1700 1700 170017001700 1700 1700 1700
690 740 790 835 875 915 955 985 1015 1045
290 335 375 415 455 495530560595625
5-ton
Y1
Y2
230 Volts
Cabinet
Size
Nominal
Airflow
CFM
CFM
RPM
WATTS
Blower
10x8
1/3
External Static Pressure - In. W.C.
625
775
3-ton
Y1
Y2
900
1200
Nominal
Cooling
Capacity
21
21
Y1
3/4
1200
1625
1375
1675
1/2
11x11
3/4
11x11
IMPORTANT:
Observe airflow operating limits. Do not operate above 1.0 in. W.C. system external static.
2-ton
Y1
Y2
4-ton
Y2
24
24
10x8
CFM
RPM
WATTS
CFM
RPM
WATTS
CFM
RPM
WATTS
CFM
RPM
WATTS
CFM
RPM
WATTS
CFM
RPM
WATTS
CFM
RPM
WATTS
CFM
RPM
WATTS
RHPL-HM
HM2421
HM3621
HM4824
HM6024