11. Electrical characteristics
Model name ROMH45AFXZJ
Power supply
Voltage V 208/230 ~
Frequency Hz 60
MCA A 28.9
Starting current A 20.1
Wiring spec. *
CKT. BKR A 30
Power cable AWG 10
*: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate
devices complied to the regional standard.
MCA: Minimum Circuit Ampacity (Calculation based on UL1995)
CKT. BKR: Circuit Breaker
DESIGN & TECHNICAL MANUAL
- 122 -
OUTDOOR UNIT
ROMH45AFXZJ