2. BASIC FREQUENCY RANGE OF COMPRESSOR
Frequency of compressor is basically defined
by operation mode as shown below.
Cooling Heating
Min Max Min Max Min Max
Dry
RP1724HJVXA 16 rps 72 rps 18 rps 90 rps 16 rps 29 rps
RP1730HJVXA 16 rps 72 rps 18 rps 90 rps 16 rps 39 rps
RP1736HJVXA 16 rps 110 rps 16 rps 117 rps 16 rps 76 rps
RP1748HJVXA 16 rps 110 rps 16 rps 117 rps 16 rps 76 rps
04-03