Detective actuators:
Detective details:
Forecast of cause :
1. Connector connection failure
2. Thermistor failure
3. Coil failure
4. 4-way valve failure
5. Main PCB failure
03-37
Indoor unit controller PCB circuit
Evaporator coil temperature thermistor
Room temperature thermistor
4-way valve
When the evaporator coil temperature is compared with the
room temperature, and either following condition is detected
continuously two times, the compressor stops.
Cooling or Dry operation
[Evaporator coil temp.] - [Room temp.] > 18°F (10°C)
Heating operation
[Evaporator coil temp.] - [Room temp.] < -18°F (-10°C)
If the same operation is repeated 5 times,
the compressor stops permanently.
Troubleshooting 27
4-way valve error
Indicate or Display:
Indoor unit
Operation lamp: 9 times Flash,
Timer lamp : 9 times Flash
Wired remote control
Error code : [E : 99]
n
: n times blinking
: Light ON: Light OFF
Mode Error
2 9
9
Outdoor unit (RP1736/1748HJVXA)
A B C D E F