EasyManua.ls Logo

Rheem RRNA-B SERIES - Wiring Diagrams

Rheem RRNA-B SERIES
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
INDOOR AIRFLOW PERFORMANCE FOR 2-5 TON PACKAGE GAS ELECTRIC UNITS
DIRECT DRIVE
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
CFM 675 [319] 657 [310] 634 [299] 602 [284] 560 [264] 505 [238] 435 [205]
RPM 695 785 870 905 940 980 1020
Watts 221 214 203 191 171 193 149
CFM 898 [424] 861 [406] 822 [388] 777 [367] 721 [340] 651 [307] 562 [265]
RPM 940 965 995 1020 1045 1070 1090
Watts 292 278 266 253 239 221 199
CFM 1076 [508] 1059 [500] 1032 [490] 996 [470] 950 [448] 896 [423] 832 [393]
RPM 730 775 820 865 905 940 975
Watts 356 349 341 331 320 305 287
CFM 1222 [577] 1197 [565] 1179 [556] 1162 [548] 1137 [537] 1097 [518] 1033 [488]
RPM 765 810 855 890 920 960 995
Watts 423 415 407 397 386 370 351
CFM 1514 [715] 1461 [670[ 1415 [668] 1370 [647] 1322 [624] 1266 [597] 1197 [565]
RPM 895 930 965 985 1005 1025 1045
Watts 538 514 493 473 454 434 412
CFM 1204 [568] 1202 [567] 1191 [562] 1171 [553] 1143 [539] 1107 [522] 1065 [503]
RPM 734 810 886 923 959 988 1016
Watts 476 468 450 427 403 380 363
CFM 1674 [790] 1620 [765] 1566 [739] 1511 [713] 1451 [685] 1384 [653] 1305 [616]
RPM 997 1019 1040 1058 1076 1088 1100
Watts 625 596 567 539 512 484 455
CFM 1843[870] 1763[832] 1693 [799] 1627 [768] 1560 [736] 1485 [701] 1398 [660]
RPM 1085 1094 1102 1110 1118 1126 1134
Watts 699 663 632 604 576 548 517
CFM 1500 [707]
RPM 896 956 1008 1062 1093 1145 1194
Watts 317 358 393 435 457 493 531
CFM 1850 [873]
RPM 1091 1141 1185 1233 1267 1308 1336
Watts 579 630 673 724 759 800 826
CFM [L/s] Air Delivery/RPM/Watts — 208 VOLTS
Side Discharge — Wet Coil
External Static Pressure — Inches W.C. [kPa]
Nominal
Cooling
Capacity
Tons [kW]
Motor Speed
From Factory
Heating
Input
BTU/HR [kW]
Blower Size/
Motor HP [W] &
# of Speeds
Motor
Speed
INDOOR AIRFLOW PERFORMANCE — 208 VOLTS
Cool Heat
Low
Low
High
Med
High
High
Med Low
Low
Low Low
High
2.0 [7.03]
2.5 [8.79]
3.0 [10.55]
40,000 [11.72]
All
Inputs
40,000 [11.72]
60,000 [17.58]
80,000 [23.45]
100,000 [29.31]
All
Inputs
60,000 [17.58]
80,000 [23.45]
100,000 [29.31]
100,000 [29.31]
60,000 [17.58]
80,000 [23.45]
9 x 7
1/4 HP
2 Speed Motor
10 x 9
1/2 HP
3 Speed Motor
10 x 9
3/4 HP
3 Speed Motor
10 x 9
1 HP ECM
(Constant CFM)
HighHigh Low3.5 [12.31]
Low
High
(See
Note
Below)
Low
Low
4.0 [14.07]
Med
High
Low
High
High5.0 [17.59]
NOTE: On 4 ton models, switch to medium speed for cooling if external static pressure is less than 0.4" W.C. at 230 volts or less than 0.3" W.C. at 208 volts.
WARNING: 1. Do not operate unit in area of airflow table shown in bold (CFM greater than 1700 for 4 ton models) due to possibility of water blow-off.
WARNING: Observe airflow operating limits if operating in area of airflow table shown in bold.
DOWN DISCHARGE PRESSURE DROP (ADD TO EXTERNAL STATIC PRESSURE)
CFM [L/s] 600 [283] 800 [378] 1000 [472] 1200 [566] 1440 [661] 1600 [755] 1800 [850] 2000 [944]
Pressure Drop—Inches W.C. [kPa] .00 .01 [.002] .02 [.005] .03 [.007] .05 [.012] .07 [.017] .08 [.019] .09 [.022]
MINIMUM RECOMMENDED FILTER SIZES
Nominal Cooling Capacity Tons [kW] 2.0 [7.03] 2.5 [8.79] – 4.0 [14.07] 5.0 [17.59]
Minimum Filter Size—Inches [mm] 20 x 20 x 1 [508 x 508 x 25] 24 x 24 x 1 [610 x 610 x 25] 24 x 30 x 1 [610 x 762 x 1]