Page 4
NOTES:
* Based on 77°F rise with 58°F potable water inlet temperature at 14 GPM heat source flow rate. Heat source temperature was 180°F.
** Minimum Coil output based on continuous boiler operation over 30 minutes. See Section III for additional considerations.
All data obtained through testing in accordance with GAMA INDIRECT-FIRED WATER HEATER TESTING STANDARD IWH-TS-1_MARCH 2003
STID30
30
1.4 119 92 27 59,000 1.5 2.3
STID40 38 2.3 198 165 33 105,000 1.5 3.4
STID50 45 2.3 205 165 40 105,000 1.1 3.4
STID80 75 2.8 259 189 70 120,000 0.8 3.5
STID120 110 2.8 291 189 102 120,000 1.2 3.5
Model
Actual Tank
Volume (gal)
Coil Volume
(gal)
First Hour
Rating (gal)*
Continuous Draw
Rating (GPH)*
First Draw
Rating (gal)*
Minimum Coil
Output (BTU/Hr)**
Standby Loss
Rating (°F/hr)
Heat Source Friction
Loss (ft. w.c. )
Table 2: Capacity & Performance
Capacities
SECTION I: SPECIFICATIONS (cont.)
NOTES:
First Hour Rating = First Draw + Continuous Draw
* Coil Input (temperature, flow rate). Ratings based on 77°F rise with 58°F inlet potable water.
All data obtained through testing in accordance with GAMA INDIRECT-FIRED WATER HEATER TESTING STANDARD IWH-TS-1_MARCH 2003
STID30
117 @ 57,000
183 @ 96,000
190 @ 96,000
245 @ 111,000
277 @ 111,000
118 @ 58,000
191 @ 101,000
198 @ 101,000
254 @ 117,000
286 @ 117,000
138 @ 71,000
214 @ 115,000
221 @ 115,000
277 @ 132,000
309 @ 132,000
144 @ 75,000
226 @ 123,000
233 @ 123,000
292 @ 141,000
324 @ 141,000
149 @ 78,000
235 @ 129,000
242 @ 129,000
304 @ 149,000
336 @ 149,000
154 @ 81,000
243 @ 134,000
250 @ 134,000
314 @ 155,000
346 @ 155,000
STID40
173 @ 89,000
STID50
180 @ 89,000
STID80
233 @ 104,000
STID120
265 @ 104,000
Model
Table 3: Performance (cont.)
FIRST HOUR RATING (gal) @ COIL OUTPUT (Btu/hr)
Performance
180°F
8 GPM*
180°F
10 GPM*
180°F
12 GPM*
200°F
8 GPM*
200°F
10 GPM*
200°F
12 GPM*
200°F
14 GPM*
115 @ 56,000