AARIA Multi MN
20
Modello / Size
250
MN
355
MN
370
MN
475
MN
485
MN
595
MN
5120 MN
Dimensioni /Dimensions
h1 / h1 m 7.5 7.5 7.5 7.5 7.5 7.5 7. 5
h2 / h2 m 7.5 7.5 7.5 7.5 7.5 7.5 7. 5
h max / h max m 15 15 15 15 15 15 15
H- / H- m 15 15 15 15 15 15 15
H+ / H+ m 15 15 15 15 15 15 15
L1, L2, L3, L4 , L5 / L1, L2, L3, L4 , L5 m 20 25 25 25 25 25 25
L1+L2+L3+L4+L5 / L1+L2+L3+L4+L5 m 30 50 60 70 70 80 100
Lunghezza massima con la carica di fabbrica /
Maximum lenght with standard charge
m 20 30 30 40 40 40 40
Carica addizionale / Additional charge g/m 20 20 20 20 20 20 20
H+
h max
h1
h1
H-
h2
L1 A
B
C
D
E
L2
L3
L4
L5
IT
10. Distanze e dislivelli
In caso di dislivelli superiori a 5 metri prevedere un
sifone ogni 5-7 metri.
Le distanze indicate sono i valori massimi consentiti.
EN
10. Distances and drops
In case of a drop in excess of 5 m, a siphon must be
installed every 5-7 metres.
The distances shown here are the maximum available
values.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Riello AARIA Multi MN Series and is the answer not in the manual?

Riello AARIA Multi MN Series Specifications

General IconGeneral
BrandRiello
ModelAARIA Multi MN Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals