EasyManua.ls Logo

Rievtech ELC Series - Page 149

Rievtech ELC Series
355 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EN
Programmable Relay User Manual for ELC, EXM and PR Series 149 2020 v6.0 © Rievtech Co.,
Ltd. www.rievtech.com
En = 0: The function sets the AQ value to 0.
En = 1: The function outputs a value at AQ, depending on
the settings of Mode and S1.
If you do not select the checkbox "when En = 0, reset
Max/Min":
En = 0: The function holds the value of AQ at the current
value.
En = 1: The function outputs a value at AQ, depending on
the settings of Mode and S1.
Mode = 0: The function sets AQ to the minimum value
Mode = 1: The function sets AQ to the maximum value
Mode = 2 and S1 = 0: The function sets AQ to the
minimum value
Mode = 2 and S1 = 1: The function sets AQ to the
maximum value
Mode = 3 or a block value is referenced: The function
outputs actual analogue input value.
Max/Min block upper/lower function
In the dialogue box of Max/Min block, there is an
upper/lower limit setting, when the block output the AQ
value is less than the lower value, the AQ shall be equal
to the Lower value; While the block output the AQ value
is more than the upper value, the AQ shall be equal to the
upper value.
If someone wants to use the upper/lower limitation for
other function blocks. such upper/lower limit function can
be used, then this block can be referenced as other blocks
parameters when programming.
Here is an example:
Someone wants to use the panel key to change the on-
delay parameters for 1s10s in the text message block, if
the value which user set exceeds such range, then it will
crush the machine, hence we must add the upper/lower
limitation in the program to avoid such trouble.

Related product manuals