4 Rinnai CVent
Water Heater Installaon
For informaon regarding the installaon of the RU98i (REU-KB3237FFUD-US), RUC98i (REU-KBD3237FFUD-US), and
C199i (REU-KBD3237FFUDC-US) tankless water heaters, please reference the Installaon and Operaon Manual
included with the respecve tankless water heater.
Set the water heater for “Long Vent” by adjusting the SW1 in DIPSW1 to the OFF Position. (Must be done on all tankless
water heaters when using CVent System)
High Altude Installaons
The Rinnai RU98i (REU-KB3237FFUD-US), RUC98i (REU-KBD3237FFUD-US), and C199i (REU-KBD3237FFUDC-US) tank-
less water heaters have been cered for use with the Common Vent System (CVent) at installaons from
0 - 10,200 feet. (0 - 3,109 m). The Common Vent System is ANSI Z21.10.3 cered; exhaust components to be
propylene (PP/PPTL) for U.S. installaons and PPS for Canadian installaons (all venng components used in Canada
must be ULC-S636 cered). Intake components to be in accordance with naonal and/or local codes having
jurisdicon.
For CVent installaons at high altude you must ensure that the water heaters are properly installed and setup for the
altude that they will be operang at.
For informaon on how to adjust altude sengs reference the respecve In-
stallaon and Operaon Manual for the RU98i (REU-KB3237FFUD-US), RUC98i (REU-KBD3237FFUD-US), and
C199i (REU-KBD3237FFUDC-US) tankless water heaters.
Water heaters using CVent at altudes over 2,000 will automacally de-rate according to the table below. Use the
tables below for calculang your total Btu for mulple water heaters using CVent at elevaon:
* RU98i (REU-KB3237FFUD-US), RUC98i (REU-KBD3237FFUD-US), and C199i (REU-KBD3237FFUDC-US)
Altude: 2,001-10,200 feet
Natural and propane gas
High Altude De-Rate plus Cvent De-Rate - LP Gas
Number
of Water
Heaters 2001-5200 Ft 5201 - 7700 Ft 7701 - 10200 Ft
1 168,000 151,000 120,000
2 332,640 298,980 237,600
3 493,920 443,940 352,800
4 651,840 585,880 465,600
5 806,400 724,800 576,000
6 957,600 860,700 684,000
7 1,105,440 993,580 789,600
8 1,249,920 1,123,440 892,800
High Altude De-Rate plus Cvent De-Rate - Natural Gas
Number
of Water
Heaters 2001-5200 Ft 5201 - 7700 Ft 7701 - 10200 Ft
1 170,000 153,000 139,000
2 336,600 302,940 275,220
3 499,800 449,820 408,660
4 659,600 593,640 539,320
5 816,000 734,400 667,200
6 969,000 872,100 792,300
7 1,118,600 1,006,740 914,620
8 1,264,800 1,138,320 1,034,160

Table of Contents

Other manuals for Rinnai REU-KB3237FFUD-US

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rinnai REU-KB3237FFUD-US and is the answer not in the manual?

Rinnai REU-KB3237FFUD-US Specifications

General IconGeneral
BrandRinnai
ModelREU-KB3237FFUD-US
CategoryWater Heater
LanguageEnglish

Related product manuals