RIVC000001 Pag. 16 REV. 00 11/10/10
UK
Code
displayed
Description/Control LED
enable
Relay
enable
Reset Mode
E1 cold room probe temperature error
if a probe is used for adjustment, the compressor will
be activated cyclically and defrosting cycles will be
disabled;
if a balanced network probe is enabled, adjustment
will continue, bypassing the malfunctioning probe
yes yes automatic when the
condition ceases
E2 End defrostin probe g error
defrosting will end due to timeout
yes yes automatic when the
condition ceases
3
rd
probe error (condenser temperature)
the associated controls are disabled
blink. no E3
3
rd
probe error (2nd evaporator temperature)
defrosting will end due to timeout
yes yes
automatic when the
condition ceases
heat alarm (*)
adjustment is disabled
yes no automatic when the
condition ceases
HP pressure switch alarm(*)
adjustment is disabled
yes no automatic when the
condition ceases
LP pressure switch alarm(*)
adjustment is disabled
yes no automatic when the
condition ceases
E4 repeated heat alarm
adjustment is disabled permanently
yes yes at switch on
E5 repeated HP pressure switch alarm
adjustment is disabled permanently
yes yes at switch on
E6 repeated LP pressure switch alarm
adjustment is disabled permanently
yes yes at switch on
LO low temperature alarm yes yes automatic when the
condition ceases
HI high temperature alarm yes yes automatic when the
condition ceases
EE data saving alarm
default parameters are loaded
yes yes at power-on or after
the parameter has
been stored to
memory
Ec condenser cleaning alarm blink. no automatic when the
condition ceases
Er network alarm (**) yes yes automatic when the
condition ceases
Ed defrosting timeout alarm blink. no automatic at the start
of the next defrost
Od door open timeout alarm
normal operation is enabled again
blink. no automatic when the
condition ceases
nx slave x alarm (on master only) yes progr. automatic when the
condition ceases
Ux slave x not connected (on master only)
the slave is not controlled
blink. no automatic when the
condition ceases
u0 master not connected (on slave only)
the slave is released from the network and operates
autonomously
blink. no automatic when the
condition ceases
dx slave x download failed(on master only) blink. no manual or automatic
when the condition
ceases
(*) The
re is no reading on the display.
(**) Network alarms are where, subsequent to programming, the alarm command is communicated from the
master to all network devices, in the event that the alarm relay is triggered on the master itself
During operation, in specific conditions the following signals are displayed:

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rivacold RIVC000001 and is the answer not in the manual?

Rivacold RIVC000001 Specifications

General IconGeneral
BrandRivacold
ModelRIVC000001
CategoryController
LanguageEnglish