EasyManua.ls Logo

robatherm RL Series - Page 33

Default Icon
83 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning and Maintenance
© robatherm 29
Maintenance
Pos: 44.8 /Inbetri ebnahme und Wartung/W artungsintervall_3Mona te/ATEX monatlic h @ 0\mod_1257930528679_20 08.doc @ 2122 @ 4
Maintenance Interval
Every three months. ATEX units every month.
Pos: 44.9 /Sicher heitshinweise/!Vor sicht_Sicherheitshi nweise beachten_Quer verweis @ 0\mod_125777 7093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 44.10 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Luftfilter_W artung_Vorsicht @ 0\mod_12 58366415225_2008.doc @ 2149 @
Caution
Allergic reactions on the skin, eyes or breathing organs can be caused by contact with filter
dusts. For maintenance and replacement works on filter cartridges wear protective clothing
and, if necessary, a respirator. Avoid contamination of the surrounding area and new filters.
Pos: 44.11 /Inbetri ebnahme und Wartung/Luftf ilter/Luftfil ter_Wartung_Ersatzf ilter @ 0\mod_125836 6506833_2008.doc @ 2150 @ 4
Replacement Filters
Keep at least one set of replacement filters in stock. Store in a dry and dust free area. Avoid
contamination and damage. Do not use filters beyond minimum durability.
Pos: 44.12 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Luftfilter_ATEX @ 0\ mod_1258365944257_20 08.doc @ 2147 @
Only use approved filter media with ATEX units.
Pos: 44.13 /Inbetri ebnahme und Wartung/Luftf ilter/Luftfil ter_Wartung @ 0\mod_125 8366603769_2008.doc @ 2151 @
Filters – Periodic Maintenance
Check filter cartridges for hygiene, contamination, odors, damage and corrosion
Particle filters: Check differential pressure with manometer
Activated carbon filters: Usually, it is enough to check the filter’s odor. (For a reliable
determination of the remaining lifetime, the manufacturer may check the filter coal’s
saturation in his lab in order to appoint proper service intervals.) Weighing of the
cartridges does not deliver feasible results, since most of the additional weight is caused
by the air’s humidity.
Check filter seat for leakage
Filters – Maintenance when necessary
Replace filter cartridges immediately if there is noticeable contamination, odor, damage
or leakage, when reaching the recommended end resistance or time interval:
1. Filter cartridge after 12 months at the latest
2. Filter cartridge after 24 months at the latest
An earlier filter change may be essential if building or conversion measures result in
significant strain on the filter or following a hygiene inspection.
The change of single filter elements is only permissible in the case of damage to individual
elements provided that the last change does not date back more than 6 months.
When changing the filter cartridges observe the local environmental protection regulations.
Pos: 45 /Layout/Seite numbruch @ 0\mod_12566286 15637_0.doc @ 2284 @

Related product manuals