EasyManua.ls Logo

Robur M50 - Page 25

Default Icon
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical installer
Installation, use and maintenance manual – M gas unit heater
25
4
Figure4.3 Connection of external request for gas unit heater
start/stop management
Z9 External request (e.g. thermostat, timer, switch, ...)
9 1110
Z9
4.4.2.2 Summer/winter mode management
How to connect the external request for
summer/winter mode management
1. Access the electrical board of the appliance according
to the Procedure 4.2
p.23
.
2. Remove the 28 temporary jumper between 1-3 termi-
nals on the internal terminal block.
3. Connect the voltage-free contact of the external re-
quest, using a 3x1 mm² cable, to 1, 2, 3 terminals of the
terminal block, as shown in Figure 4.4
p.25
.
The cable may not be longer than 20 metres.
Figure4.4 Summer/winter switch connection
Z1 Summer/winter
switch
1 2 3
Z1
4.4.2.3 Control of multiple gas unit heaters with a
single external request
Through a suitable connection to the terminals described
above, it is possible to manage the specic function on
more than one gas unit heater using a single external
request.
The centralised management of the on/o switch can be
carried out as described in Figure 4.5
p.26
, using a time
programmer and several room thermostats. The presence
of the room thermostats serving each generator allows to
activate the generator itself only when the specic area
has a real need for heat, avoiding waste of energy. The
presence of a time programmer makes it possible to sub-
ordinate the ignition of the heater, even in the presence
of a request from the room thermostat, to a centralised
consent.

Other manuals for Robur M50

Related product manuals