EasyManuals Logo
Home>Rockwell Automation>Touch terminals>PanelView Plus 1000

Rockwell Automation PanelView Plus 1000 User Manual

Rockwell Automation PanelView Plus 1000
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #94 background imageLoading...
Page #94 background image
94 Publication 2711P-UM001I-EN-P - December 2008
Chapter 4 Configuration Mode
Enter Configuration Mode on Startup
Follow these steps to enter Configuration mode on startup.
1. Select Terminal Settings>Startup Options>FactoryTalk View ME
Station Startup.
2. Press the On Startup button to select Go to Configuration Mode.
3. Press the Configuration Mode Options button.
4. Press the Load Current Application button to specify whether
you want to load the current application on startup.
5. Press the Replace RSLinx Communications button to specify
whether to use the communication configuration of the current
application or the terminal on startup.
Select No to use the RSLinx configuration of the terminal.
Select Yes to use the configuration of the application. The
terminal configuration is replaced with the application
settings. Any changes to device addresses or driver properties
in RSLinx communication will be lost.
6. Press OK to return to the previous screen.
7. Press OK to return to Terminal Settings.

Table of Contents

Other manuals for Rockwell Automation PanelView Plus 1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PanelView Plus 1000 and is the answer not in the manual?

Rockwell Automation PanelView Plus 1000 Specifications

General IconGeneral
BrandRockwell Automation
ModelPanelView Plus 1000
CategoryTouch terminals
LanguageEnglish

Related product manuals