FA ROTEX RoCon HP - 03/2013
4 x Faults and malfunctions
Room cooling does not
cool
Water flow too low.
Ɣ Check that all stop valves of the water circuit are
completely open.
Ɣ Check that the expansion tank is defective.
Ɣ Bleed system completely.
Ɣ On the controller (rotary switch setting "Info" )
check whether there is adequate water pressure
(> 0.3 bar).
Ɣ Check that the resistance in the water circuit is not too
high for the pump (see installation manual for
"Technical Data").
"cooling" turned off (e.g. switching time pro-
gramme is in the setback phase, exterior tem-
perature too low).
Ɣ Check the operating mode setting.
Ɣ Check the request parameters.
Ɣ Check the setting of time a weekday in the control
system.
Refrigerant compressor is not working.
Ɣ Wait until minimum water temperature is reached
(15 °C). At a low water temperature the system may
use the optional backup heater (BUH) first to reach the
minimum water temperature.
Ɣ Have the system checked by a ROTEX heating
technician.
System is in the operating mode "heating". Ɣ Switch the operating mode to "cooling".
Cooling effect of room
cooling too little
Water flow too low.
Ɣ Check that all stop valves of the water circuit are
completely open.
Ɣ Check that the water filter is dirty.
Ɣ Check that the expansion tank is defective.
Ɣ Bleed system completely.
Ɣ On the controller (rotary switch setting "Info" )
check whether there is adequate water pressure
(> 0.3 bar).
Ɣ Check that the resistance in the water circuit is not too
high for the pump (see installation manual for
"Technical Data").
Water volume in system too low
Ɣ Check water volume and associated primary pressure
in expansion container, top-up water level if necessary
and reconfigure primary pressure (see installation
manual for "Minimum Flow").
Quantity of refrigerant in the system too low or
too high.
Ɣ Have coolant level checked by a ROTEX technician.
Have him check the system for leaks.
Circulation pump is being
excessively noisy while
running
Air in the water circuit Ɣ Bleed the entire water circuit.
Noises caused by vibrations.
Ɣ Check the HPSU compact, its components and covers
to ensure they are fastened correctly.
Bearings damage in the circulation pump. Ɣ Reduce speed of pump, replace circulation pump.
Water pressure at pump inlet too low.
Ɣ On the controller (rotary switch setting "Info" )
check whether there is adequate water pressure
(> 0.3 bar).
Ɣ Check that the pressure gauge is working correctly
(connect an external pressure gauge).
Ɣ Check that the expansion tank is not defective and that
the primary pressure has been set correctly (see
installation manual).
Malfunction Possible cause Possible solution

Other manuals for Rotex HPSU compact 304

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rotex HPSU compact 304 and is the answer not in the manual?

Rotex HPSU compact 304 Specifications

General IconGeneral
BrandRotex
ModelHPSU compact 304
CategoryController
LanguageEnglish

Related product manuals