Roxtec R Series User Manual

Default Icon
4 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Roxtec R 50 frame
Roxtec Lubricant
Roxtec R 70/75 frame Roxtec R 100-200 frame
Roxtec RM sealing module
(not included)
W
H
SW
Technical data
Components
Frame Aperture
A Ø (mm)
Clearance depth
L (mm)
Packing space
(HxW)
Tool size
SW (mm)
Approx. torque*
(Nm)
R 50 50-52 73
30x30 3 5-6
R 70 70-72 71
40x40 10 6-7
R 75 75-77 71
40x40 10 6-7
R 100 100-102 75
60x60 10 6-7
R 125 125-127 71
80x80 10 6-7
R 127 127-129 71
80x80 10 6-7
R 150 150-152 71
90x90 13 9-11
R 200 200-202 71
120x120 13 9-11
∅A
L
ØA
* The amount of torque needed to compress the seal depends on several things, e.g cable or pipe size,
amount of used lubricant, aperture size or material in the cable sheath, etc.
Safetyinformation
Roxtec recommends that all installations
are performed without facility operation.
Follow national regulations and installation
codes. Any action affecting the routed
service should be performed according to
manufacturer recommendations.
Installation instructions
Roxtec R transit
Question and Answer IconNeed help?

Do you have a question about the Roxtec R Series and is the answer not in the manual?

Roxtec R Series Specifications

General IconGeneral
Product TypeCable and pipe transit
ApplicationSealing cables and pipes
Fire resistanceYes, certified fire protection (exact rating varies by model)
Water tightnessYes, depending on model and installation
Gas tightnessYes, depending on model and installation
Area of useIndustrial, commercial, and marine applications

Summary

Installation Methods

Installation in a core drilled hole

Procedure for installing the Roxtec system using a hole saw of the appropriate diameter.

Installation in a non-load-bearing structure

Method for non-load-bearing structures, involving adding framing to the existing structure.

Installation of bolted sleeve

Attaching the sleeve to the structure using a suitable sealing method and fasteners.

Installation in a welded sleeve

Welding the Roxtec sleeve to the structure, with guidelines available online.

Installation R frame

Frame Installation Steps

Step-by-step guide for installing the Roxtec R frame, including lubrication and module fitting.

Module Adaptation and Installation

Instructions for adapting modules by peeling layers and installing them with cables/pipes.

Compression and Tightening

Guidance on tightening nuts crosswise for proper compression and signs of good installation.

Disassembly and Reinstallation

Disassembly Process

Steps for untightening nuts, removing modules, and cleaning surfaces for reinstallation.

Reinstallation Instructions

Guidance for reassembling the frame and continuing the installation process.

Pre-routed Cables/Pipes

R70/75 Pre-routed Procedure

Instructions for disassembling and orientating fittings for pre-routed cables/pipes.

R100 Pre-routed Procedure

Steps for partially disassembling the seal and cutting for pre-routed cables.

R125-R200 Pre-routed Procedure

Method to cut the side open between screws for pre-routed cables/pipes.