EasyManua.ls Logo

Runxin F79A-LCD - 3.4. Parameter settlement; Service Time Calculation; Backwash Time Calculation; Brine & Slow Rinse Time Calculation

Default Icon
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MODEL 82602-F79A-LCD/82602B-F79B-LCD/82604-F82A-LCD/82604B-F82B-LCD
28
3.4. Parameter settlement
Service TimeT1
Water Treatment Capacity:
Q=V
R
×K÷Y
D
m
3
Hardness of Inlet Water, mmol/L.
Exchange factor, mmol/L, 4001000.
Down-flow regeneration 400 750
Up-flow regeneration, take 4501000.
If the inlet water hardness is higher, the
factor is smaller.
Resin volumem
3
.
By hoursT1=Q÷Q
h
Hour
Water treatment capacity ( m
3
/h )
Water treatment capacitym
3
By days T1=Q÷Q
d
Day
Water treatment capacity per day (m
3
/d)
Water treatment capacity (m
3
)
T2 Backwash time T2
It is subject to the turbidity of inlet water. Generally, it is suggested to
be set 1015 minutes. The higher the turbidity is, the longer backwash
time shall be set. However, if the turbidity is more than 5FTU, it is better to
install a filter in front of the exchanger.
Brine& slow rinse time (Slow rinse time is also replacement time)
aBrine time=60×V
Z
/(S×v) (min.)
V
Z
=m
cz
/(C×ρ×10
3
) (m
3
)
In this formulaV
Z
——Regeneration fluid volume (m
3
)
S——Cross-sectional area of exchanger layer (m
2
)
v——Regeneration fluid flow rate (m/h)
Mcz——The amount of reagent when regenerate reach to

Related product manuals