MODEL 82602-F79A-LCD/82602B-F79B-LCD/82604-F82A-LCD/82604B-F82B-LCD
40
11.Interrupted
or irregular
brine.
A. Water pressure too low
or not stable.
B. Injector is plugged or
faulty.
C. Air in resin tank.
D. Floccules in resin tank
during backwash.
A. Increase water pressure.
B. Clean or replace injector.
C. Check and find the reason.
D. Clean the floccules in resin
tank.
12.Water flow
out from drain
or brine pipe
after
regeneration.
A. Foreign material in valve
which makes valve can’t be
closed completely.
B. Hard water mixed in
valve body.
C. Water pressure is too
high which result in valve
doesn’t get the right
position.
A. Clean foreign material in valve
body.
B. Change valve core or sealing
ring.
C. Reduce water pressure or use
pressure release function.
Control Valve Fault(Continue)
13. Salt
water in
soften water.
A. Foreign material in
injector or injector fails to
work.
B. Brine valve cannot be
shut-off.
C. Time of fast rinse too
short.
A. Clean and repair injector.
B. Repair brine valve and clean it.
C. Extend fast rinse time.
14. Circle
capacity
decreases.
A. Regenerate not properly.
B. Fouled resin bed.
C. Salt setting not proper.
D. Softener setting not
proper.
E. Raw water quality
deterioration.
F. Turbin has already been
stucked.
A. Regenerate according to right
way.
B. Increase backwash flow rate
and time, clean or change resin.
C. Readjust brine drawing time.
D. According to the test of outlet
water, recount and reset.
E. Regenerate unit by manual
temporary then reset regeneration
cycle.
F. Disassemble flow meter and
clean it or replace a new turbine.