ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION.
3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955
INSTALLATION INSTRUCTIONS
1
1
/2 HOUR UL CLASSIFIED
CURTAIN TYPE (D)IBD2, (D)IBD2SS AND (D)IBDT FIRE DAMPERS
APPLICATION
The fire damper models shown on this sheet are marked with a
1
1
/2 hour fire damper label and are approved for use in fire walls or
masonry floors with ratings of less than 3 hours. Fire Dampers
require a field-or factory-installed sleeve. Select a sleeve of suffi-
cient length to permit mounting angles attachment. Static and
Dynamic dampers must be installed with leading edge of the
closed blades within the wall or floor.
STATIC FIRE DAMPERS – IBD models
N
ot for use in Dynamic (fans on) Systems.
MODEL IBD2 MAXIMUM SIZE
Single Section
Vertical Installation 48"w x 30"h or 33"w x 72"h (1219 x
762 or 838 x 1829) or 36"w x 36"h (914 x 914).
Horizontal Installation 30"w x 45
1
/2"h (762 x 1156) or 33"w
x 38"h (838 x 965).
Multiple Section Assembly
Vertical Installation – 120"w x 72"h (3048 x 1829).
Horizontal Installation – 90"w x 91"h (2286 x 2311) or 114"w x
38"h (2896 x 965).
MODEL IBD2SS MAXIMUM SIZE
Single Section
Vertical Installation 48"w x 30"h or 33"w x 72"h (1219 x
762 or 838 x 1829) or 36"w x 36"h (914 x 914).
Horizontal Installation 30"w x 45
1
/2"h (762 x 1156) or 33"w
x 38"h (838 x 965).
Multiple Section Assembly
Vertical Installation – 99"w x 72"h (2515 x 1829).
Horizontal Installation – 90"w x 91"h (2286 x 2311) or 114"w x
38"h (2896 x 965).
MODEL IBDT, IBDT1 and IBDT2 MAXIMUM SIZE
Single Section
Vertical Installation – 40"w x 48"h (1016 x 1219).
Horizontal Installation – 36"w x 36"h (914 x 914).
Notes:
1. Dimensions shown in parentheses ( ) indicate millimeters.
2. All multiple section dampers are constructed of equal single
section sizes no greater than the maximum single section sizes
indicated above
II-IBD-618/Replaces II-IBD-616 © Ruskin June 2018
DYNAMIC FIRE DAMPERS
Use in Dynamic (fans on) or Static (fans off) Systems
MODEL DIBD2 MAXIMUM SIZE
Single Section
Vertical Installation – 33"w x 36"h (838 x 914).
Horizontal Installation – 24"w x 24"h (610 x 610).
Multiple Section Assembly
Vertical Installation 72"w x 48"h (1828 x 1219) or 48"w x
72"h (1219 x 1828) or 120"w x 24"h (3048 x 610).
MODEL DIBD2X MAXIMUM SIZE
Single Section
Vertical Installation – 18"w x 24"h (457 x 610).
Horizontal Installation – 18"w x 24"h (457 x 610) or 24"w x
18" h (610 x 457).
Multiple Section Assembly
Horizontal Installation 36"w x 48"h (914 x 1219) or 48"w x
36"h (1219 x 914).
MODEL DIBD2SS MAXIMUM SIZE
Single Section
Vertical or Horizontal Installation – 24"w x 24"h (610 x 610).
Multiple Section Assembly
Vertical Installation 72"w x 48"h (1828 x 1219) or 48"w x
72"h (1219 x 1828) or 90”w x 24”h (2286 x 610).
MODEL DIBDT, DIBDT1 and DIBDT2 MAXIMUM SIZE
Single Section
Vertical Installation – 24”w x 24”h (610 x 610).
INSTALLATION SUPPLEMENTS
Refer to the appropriate Ruskin installation instruction supplements
for additional information or special requirements:
Optional Sealant of Dampers in Fire Rated Wall or Floor
Openings
Transfer Openings and Duct Terminations
Optional FireStop Material
Extension of Fire and Combination Fire and Smoke Damper
Sleeves
Fire and Combination Fire/Smoke Dampers Installation in
Concrete Floor with Steel Deck
Drivemate No. 14880 Breakaway Connection
Flanged System Breakaway Connections
Mullions for Dampers in Oversized Concrete Wall Openings
California State Fire Marshal Listing No. 3225-245:005
SEE COMPLETE MARKING
ON PRODUCT
Question and Answer IconNeed help?

Do you have a question about the Ruskin DIBD2 and is the answer not in the manual?

Ruskin DIBD2 Specifications

General IconGeneral
ModelDIBD2
CategoryFire and Smoke Dampers
TypeDynamic
ApplicationHVAC systems
ActuationElectric or Pneumatic
Temperature Rating250°F (121°C)
Leakage ClassClass I
UL RatingUL 555 and UL 555S
ConstructionGalvanized Steel