ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION.
3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955
INSTALLATION INSTRUCTIONS
FSD60-3 and FSD60-3M COMBINATION FIRE AND SMOKE DAMPER
3 HOUR UL555 RATED UL555S LEAKAGE CLASS 1 RATED
II-FSD60-3-0121/ Replaces II-FSD60-3-316
© Ruskin January 2021
INSTALLATION SUPPLEMENTS
Refer to the appropriate Ruskin installation instructions supple-
ments for additional information or special requirements:
Optional Sealant of Dampers in Fire Rated Wall or Floor Openings
Transfer Openings and Duct Terminations
Optional FireStop Material
Extension of Fire and Combination Fire and Smoke Damper
Sleeves
Fire and Combination Fire and Smoke Damper Installation in
Concrete Floor with Steel Deck
Drivemate No. 14880 Breakaway Connection
Flanged System Breakaway Connections
TS150 FireStat for "Reopenable" Combination Fire and Smoke
Dampers
SP100 Switch Package
EFL Electric Resettable "Fuse" Link
EFL/SP100 Electric Resettable "Fuse" Link and Switch Package
PFL Pneumatic Fuse Link
DSDF Flow Rated Duct Smoke Detector
DSDN No-Flow Rated Duct Smoke Detector
APPLICATION
The FSD60-3 combination fire and smoke damper is designed to
restrict the passage of flame and resist the passage of smoke. The
FSD60-3 is designed for installation with the blades running hori-
zontally. The standard installation is with the leading edge of the
closed blades within the wall, partition, or masonry floor with a fire
resistance rating of 3 hours or more.
FSD60-3 MAXIMUM UL CLASSIFIED SIZES –
OPPOSED BLADE
Single section vertical – 30"w x 48"h (762 x 1219)
Single section horizontal – 30"w x 48"h (762 x 1219)
Multiple sections vertical – 120"w x 96"h (3048 x 2438)
Multiple sections horizontal – 144"w x 96"h (3658 x 2438)
FSD60-3M MAXIMUM UL CLASSIFIED SIZES –
OPPOSED BLADE
Single section vertical – 30"w x 48"h (762 x 1219)
Single section horizontal – 30"w x 48"h (762 x 1219)
Multiple sections vertical 120"w x 96"h (3048 x 2438)
60"w x 96"h (1524 x 2438)
Multiple sections horizontal 120"w x 96"h (3048 x 2438)
60"w x 96"h (1524 x 2438)
Note: Dimensions shown in parentheses ( ) indicate millimeters.
California State Fire Marshal Listing No.
FSD60-3 and 60-3M - 3235-0245:0126 NYC
Department Of Building MEA 252-05-E