6. DIP SWITCHES
FUNCTION
DESCRIPTION
6. DIP SWITCHES FUNCTION DESCRIPTION
6. DIP SWITCHES FUNCTION DESCRIPTION
ON = Encoder is powered from MicroZed v3.5
Not used
OFF = Hardware implementation of EOS DNI and EOS UPI is enabled,
this mean whenever EOS DNI/EOS UPI opens when lift is going
in the down/up direction, speed reference signals (High, Low,
Intermediate) are immediately removed. This will force VVVF drive
to ramp to zero speed and stop.
OFF = Hardware implementation of EOS DN and EOS UP is activated,
this mean whenever EOS DN/EOS UP opens when lift is going
in the down/up direction, speed reference signals (High, Low,
Intermediate) are immediately removed. This will force VVVF drive
to ramp to zero speed and stop
1 2 3
4
ON
In AC2 speed, Hydraulic and VVVF with no direct approach, dip switches 1 & 2 must be kept on.